Plan Review Notes
Plan Review Notes For Permit 13060089
Permit Number 13060089
Review Stop B
Sequence Number 2
Notes
Date Text
2013-08-12 17:26:13RESIDENTIAL (R3) RENOVATION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- IF WINDOWS TO BE REPLACED HAVE NOT IMPACT GLASS,
 THEN SPECIFY SAFETY GLASS FOR BATHROOM WINDOW, WINDOW
 IN MASTER BEDROOM CLOSET AND WINDOW BY THE DOOR OF
 GUEST BEDROOM ROOM #3. SEC. R308.4
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL TYPE OF WINDOWS SHOWN ON PLANS. (REPEAT COMMENT.
 NO ADDRESSED).
  
 B) ALL EXTERIOR DOORS THAT ARE GOING TO BE REPLACED.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 C) WINDOW MULLIONS AS SHOWN ON PLANS. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 D) HURRICANE SHUTTERS, IF DOORS AND WINDOWS GLAZING IS
 NO HURRICANE IMPACT RESISTANT. NOTE: ALSO NEED TO
 PROVIDE COMPLETE INSTALLATION DETAIL. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL. SEC.
 107.3.4.1 CITY AMENDMENTS. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712