2013-08-12 17:26:13 | RESIDENTIAL (R3) RENOVATION SECOND BUILDING REVIEW | | CHECKLIST. | | CODE: 2010 FBC. | | | | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. | | | | 2- IF WINDOWS TO BE REPLACED HAVE NOT IMPACT GLASS, | | THEN SPECIFY SAFETY GLASS FOR BATHROOM WINDOW, WINDOW | | IN MASTER BEDROOM CLOSET AND WINDOW BY THE DOOR OF | | GUEST BEDROOM ROOM #3. SEC. R308.4 | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR: | | A) ALL TYPE OF WINDOWS SHOWN ON PLANS. (REPEAT COMMENT. | | NO ADDRESSED). | | | | B) ALL EXTERIOR DOORS THAT ARE GOING TO BE REPLACED. | | (REPEAT COMMENT. NOT ADDRESSED). | | | | C) WINDOW MULLIONS AS SHOWN ON PLANS. (REPEAT COMMENT. | | NOT ADDRESSED). | | | | D) HURRICANE SHUTTERS, IF DOORS AND WINDOWS GLAZING IS | | NO HURRICANE IMPACT RESISTANT. NOTE: ALSO NEED TO | | PROVIDE COMPLETE INSTALLATION DETAIL. (REPEAT COMMENT. | | NOT ADDRESSED). | | | | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL. SEC. | | 107.3.4.1 CITY AMENDMENTS. (REPEAT COMMENT. NOT | | ADDRESSED). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|