 438 36TH STREET
 SF REMODEL ? 2 UNITS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 SHOW THE ELECTRIC SERVICE AND PANEL BOARD LOCATIONS.
 INDICATE THE FAULT CURRENT CAPABILITY OF THE ELECTRICAL
 SERVICE DISCONNECTS AND PANEL BOARDS. INCLUDE PANEL
 SCHEDULES. NEC 110.9, 215.5
  
 BASED ON THE SUPPLIED ELECTRICAL CALCULATION THE
 PROPOSED ELECTRIC SERVICE IS TOO SMALL. PLEASE CLARIFY.
 NEC 230.31
  
 THE ALUMINUM CONDUCTORS ARE UNDERSIZED. NEC T. 310.16
  
 GROUNDING AND BONDING OF PANEL BOARDS AT SEPARATE
 BUILDINGS SHALL INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR AND A GROUNDING ELECTRODE. NEC 250.32 (A) AND
 (B)
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)(3)
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE
 FRONT AND BACK ENTRANCE AREAS. NEC 210.52 (E) (1)
  
 A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE
 GROUND NEC 250.94
  
  