2013-07-08 12:02:50 | | | 13060089 | | 438 36TH STREET | | SF REMODEL ? 2 UNITS | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | SHOW THE ELECTRIC SERVICE AND PANEL BOARD LOCATIONS. | | INDICATE THE FAULT CURRENT CAPABILITY OF THE ELECTRICAL | | SERVICE DISCONNECTS AND PANEL BOARDS. INCLUDE PANEL | | SCHEDULES. NEC 110.9, 215.5 | | | | BASED ON THE SUPPLIED ELECTRICAL CALCULATION THE | | PROPOSED ELECTRIC SERVICE IS TOO SMALL. PLEASE CLARIFY. | | NEC 230.31 | | | | THE ALUMINUM CONDUCTORS ARE UNDERSIZED. NEC T. 310.16 | | | | GROUNDING AND BONDING OF PANEL BOARDS AT SEPARATE | | BUILDINGS SHALL INCLUDE AN EQUIPMENT GROUNDING | | CONDUCTOR AND A GROUNDING ELECTRODE. NEC 250.32 (A) AND | | (B) | | | | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. | | NEC 210.11 (C)(3) | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE | | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A | | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | R313 | | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT THE | | FRONT AND BACK ENTRANCE AREAS. NEC 210.52 (E) (1) | | | | A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE | | GROUND NEC 250.94 | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | | | | | |
|