2013-07-18 11:25:12 | RESIDENTIAL (R3) RENOVATION/ALTERATION, BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- ACCORDING TO PALM BEACH COUNTY PROPERTY APPRAISAL |
| AND CITY RECORDS, THERE IS ONLY ONE SINGLE FAMILY |
| RESIDENCE FOR THIS PROPERTY. THE REAR BUILDING HAS |
| STORAGE AND GARAGE ON THE FIRST FLOOR. THERE ARE NO |
| PERMITS FOR THE CONVERSION TO A DWELLING UNIT. PLANS |
| NEED TO BE REVISED TO REFLECT PROPOSED USE AND NUMBER |
| OF DWELLING UNITS. PLANS TO PROVIDE THE FOLLOWING: |
| |
| A) DESIGN PRESSURES FOR DOORS AND WINDOWS. SEC. |
| R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. |
| |
| B) COMPLETE DETAILS AND SPECIFICATIONS FOR THE TWO |
| FAMILY DWELLINGS FIRE RATED SEPARATION AS REQUIRED BY |
| SEC. R302.3. (***NOTE: SPECIFIED ASSEMBLY NEED TO BE |
| TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263). |
| |
| C) COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| DWELLING/GARAGE SEPARATION AS REQUIRED BY SEC. R302.5 |
| AND SEC. R302.6. |
| |
| D) BATHROOMS VENTILATION AS REQUIRED BY SEC. R303.3. |
| |
| E) HEATING AS REQUIRED BY SEC. R303.8. |
| |
| F) MINIMUM ROOM DIMENSIONS. SEC. R304. (***NOTE: |
| BEDROOM ON SECOND FLOOR OF REAR BUILDING SCALES LESS |
| THAN 7'-0". THIS DIMENSION TO BE VERIFIED IN FIELD AT |
| TIME OF INSPECTION). |
| |
| G) TOILET, BATH AND SHOWER FIXTURE CLEARANCES TO COMPLY |
| WITH SEC. R307 AND FIGURE R307.1. |
| |
| H) GLAZING HAZARDOUS LOCATIONS AS REQUIRED BY SEC. |
| R308.4. |
| |
| I) BEDROOM EMERGENCY EGRESS AS REQUIRED BY SEC. R310 |
| FOR FIRST AND SECOND FLOOR BEDROOM. SPECIFY SIZE AND |
| TYPE OF ALL BEDROOM WINDOWS.WINDOWS. |
| |
| J) MEANS OF EGRESS AS REQUIRED BY SEC. R311. SPECIFY |
| SIZE OF ENTRY DOOR TO EACH DWELLING UNIT. AND CLEARLY |
| IDENTIFY WHICH DOORS ARE GOING TO BE REPLACED. |
| |
| K) STAIRWAY ON SECOND FLOOR DWELLING UNIT ON REAR |
| BUILDING DOESN'T COMPLY WITH THE LANDING EGRESS |
| REQUIREMENT OF SEC. R311.3. |
| |
| L) CARBON MONOXIDE ALARMS AS REQUIRED BY SEC. R315. |
| |
| 2- PLANS NEED TO HAVE THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 3- CLEARLY SPECIFY ON PLANS THE ALTERATION LEVEL AS |
| REQUIRED BY SEC. 401.4, SEC. 406 AND/OR SEC. 408 OF |
| 2010 FBC-EXISTING BUILDING. |
| |
| 4- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD) TO CHECK IF IMPACT FEES ARE |
| DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF THE |
| PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| 5- THERE ARE TWO BUILDINGS ON THIS PROPERTY. PROVIDE A |
| PERMIT APPLICATION FOR EACH BUILDING. SEC. 105.1 AND |
| SEC. 107.2.1.4 OF CITY AMENDMENTS TO FBC. |
| |
| 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) ALL TYPE OF WINDOWS SHOWN ON PLANS. FOR EXAMPLE; |
| FIXED WINDOWS, ARCHED WINDOWS, SINGLE HUNG WINDOWS, |
| ETC. |
| |
| B) ALL EXTERIOR DOORS THAT ARE GOING TO BE REPLACED. |
| CLEARLY IDENTIFY ON PLANS DOORS TO BE REPLACED. |
| |
| C) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY |
| IDENTIFY MULLION SIZE AND ANCHORING TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| R301.2.1.4.3. |
| |
| D) HURRICANE SHUTTERS, IF DOORS AND WINDOWS GLAZING IS |
| NO HURRICANE IMPACT RESISTANT. NOTE: ALSO NEED TO |
| PROVIDE COMPLETE INSTALLATION DETAIL. |
| |
| 7- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL. SEC. |
| 107.3.4.1 CITY AMENDMENTS. |
| |
| 8- CLARIFY HOW DO YOU ENTER GUEST BEDROOM #2 ON MAIN |
| HOUSE?. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 9- SHEET ONE: |
| A) FLOOR PLANS DON'T MATCH EXISTING CONDITIONS. SEC. |
| 107.2.1 CITY AMENDMENTS TO FBC. NOTE: THIS IS A |
| HISTORIC CONTRIBUTING HOUSE. BUILDING FACADES CAN'T BE |
| ALTERED. SEE HISTORIC COMMENTS. (WE HAVE PICTURES OF |
| THE EXISTING FACADES. PLANS SUBMITTED DON'T MATCH THE |
| PICTURES. EXISTING OUTSIDE STAIRS ARE NOT CONCRETE. |
| ALSO, WHERE IS THE FIREPLACE?). |
| |
| B) PLANS SHOWN ON FIRST SHEET DON'T MATCH PLANS SHOWN |
| ON THE ELECTRICAL PLANS ON SHEET A-2. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| C) REVISE GENERAL NOTES ON SHEET ONE. COORDINATE WITH |
| ITEMS #7A) AND 7B) ABOVE. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| D) CLARIFY WINDOW LEGEND. WHY WINDOW "A" SAYS "OPTIONAL |
| FOR C". WINDOW SIZES ARE DIFFERENT. IT CAN'T BE |
| OPTIONAL. SEC. 107.2.1 CITY AMENDMENTS. NOTE: WINDOW |
| "A" DOESN'T COMPLY WITH EGRESS REQUIREMENTS SEC. R310. |
| CLEARLY SPECIFY THE SIZE OF EXISTING OPENING. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| E) ALL THE INTERIOR AND OUTSIDE STAIRS ARE SHOWN |
| INCORRECTLY. FOR EXAMPLE SECOND FLOOR STEPS NEED TO BE |
| SHOWN SOLID NOT DOTTED LINES. AND, THERE IS NOTHING |
| BELOW THE EXISTING STAIRS. VISIT SITE AND REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |