2013-07-05 11:54:49 | BUILDING PLAN REVIEW |
| PERMIT: 13060068 |
| ADD: 1475 CENTREPARK BLVD # 140 |
| CONT: CHANDLIER CONSTRUCTION |
| TEL: (561)791-6934 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: JULY 05/2013 |
| ACTION: DENIED |
| |
| NOTE: WHERE THERE ARE DIFFERENCES BETWEEN TWO CODES, |
| THE MOST STRIGENT SHALL APPLY. |
| |
| 1) SHEET A-2 THE BREAK ROOM IS APPROXIMATELY 835 SQ FT, |
| SINCE THIS AREA IS OVER THE 750 SQ FT EXCEPTION 3 OF |
| 303.1 IT DOES CONSTITUTE AN A2 OCCUPANCY HAVING TO MEET |
| THE FOLLOWING: |
| 1A) 2010 FBC-B TABLE 1015.1 EXCEEDS 49 OCCUPANTS WILL |
| NEED TWO MEANS OF EGRESS |
| 1B) 2010 FBC-B 1015.2.1 EXC # 2 THE EXIT DOORS NEED TO |
| BE A MINIMUM OF 1/3RD THE LONGEST DIAGONAL DISTANCE |
| APART. |
| 1C) 2010 FBC-B 1014.3 EXC # 1 100 FT COMMON PATH OF |
| TRAVEL IS EXCEEDED, BOTH DOORS FROM THE BREAK ROOM LEAD |
| TO THE SAME COMMON PATH OF TRAVEL UNTIL YOU HAVE A |
| CHOICE OF TRAVEL AT THE FRONT ENTRY. |
| |
| 2) THE CONFERENCE ROOM BY ITSELF BECAUSE IT IS UNDER |
| 750 SQ FT WOULD BE CONSIDERED BUSINESS OCCUPANCY PLEASE |
| PROVIDE DOCUMENTATION THAT THE COMBINED ASSEMBLY USAGE |
| AREAS FOR THE WHOLE FLOOR DOES NOT EXCEED 10% OF THE |
| FLOOR AREA AREA LIMITATION 508.2.1 THEN UNDER THE 2010 |
| FBC-B THE CONFERENCE ROOM WOULD BE CONSIDERED BUSINESS |
| OCCUPANCY. |
| |
| SEE BOAF INFORMAL INTERPRETATION 6506 |
| BOAF |
| INFORMAL INTERPRETATION |
| REPORT NUMBER 6506 |
| |
| DATE: THU JUN 3 2010 |
| REPORT: 6506 |
| CODE: BUILDING CODE YEAR: 2007 |
| SECTION: 508.3.1 |
| QUESTION: |
| IS IT THE INTENT OF FLORIDA BUILDING CODE - BUILDING |
| SECTION 508.3.1, EXCEPTION 1, TO NOT REQUIRE FIRE |
| SEPARATION BETWEEN THE |
| PRIMARY OCCUPANCY AND MULTIPLE ACCESSORY OCCUPANCIES, |
| WHEN EACH ACCESSORY OCCUPANCY IS LESS THAN 750 SQ. FEET |
| EACH OR |
| ONLY WHEN THE TOTAL OF ALL ACCESSORY OCCUPANCIES IS |
| LESS THAN 750 SQ. FEET IN AREA? |
| COMMENT: |
| AN EXAMPLE WOULD BE A BUSINESS OCCUPANCY WITH ONE |
| ACCESSORY AREA OF 700SF FOR GATHERINGS AND MEETINGS AND |
| A SECOND |
| ACCESSORY AREA OF 650SF FOR FITNESS AND WORKOUT. IS THE |
| EXCEPTION LIMITATION OF 750 S.F. MAX APPLIED TO EACH |
| ACCESSORY AREA, IN |
| WHICH CASE THIS BUILDING WOULD COMPLY, OR TO THE |
| COMBINED TOTAL OF THE TWO ACCESSORY AREAS, IN WHICH |
| CASE IT WOULD NOT? |
| ANSWER: |
| NO. CONSIDERING BOTH SPACES TO BE ASSEMBLY USES LOCATED |
| ON THE SAME FLOOR, THE EXCEPTION TO FLORIDA BUILDING |
| CODE - BUILDING |
| SECTION 508.3.1 WOULD NOT REQUIRE SEPARATION OF EITHER |
| SPACE. HOWEVER, THE SECTION TO WHICH THE EXCEPTION |
| RELATES WOULD LIMIT THE AGGREGATE ACCESSORY OCCUPANCIES |
| TO 10% OF THE AREA OF THE FLOOR ON WHICH THEY ARE |
| LOCATED. IF THE AREA OF TWO COMBINED ASSEMBLY USES |
| EXCEEDED 10%, THEN AT LEAST ONE OF THE ASSEMBLY USES |
| WOULD REQUIRE FIRE RESISTANT RATED SEPARATION OF 2 |
| HOURS IN A NON-SPRINKLED BUILDING AND 1 HOUR IN A |
| BUILDING SPRINKLED THROUGHOUT. |
| |