2013-06-05 10:56:58 | 5200 NORTH FLAGLER DRIVE |
| PERMIT #13060053 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| PLANS SHOW A 4-BURNER RANGE IN THE KITCHEN AREA. |
| COOKING OPERATIONS THAT MAY RESULT IN THE PRODUCTION OF |
| SMOKE OR GREASE-LADEN VAPORS SHALL BE PROTECTED WITH A |
| CLASS I MECHANICAL EXHAUST HOOD EQUIPPED WITH AN |
| AUTOMATIC WET-CHEMICAL FIRE SUPPRESSION SYSTEM. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF |
| HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY |
| (ASSEMBLY) OF THE SPACE, SHALL BE SEPARATED FROM |
| NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR |
| BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS |
| SHALL BE SELF CLOSING, POSITIVE LATCHING, AND |
| FIRE-RATED FOR AT LEAST 45-MINUTES. |
| |
| EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM |
| OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL |
| LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE |
| ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT |
| LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, |
| NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF |
| EGRESS AT FLOOR LEVEL. |
| |
| FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 |
| OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON |
| DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR |
| LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE |
| PANIC HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE |
| MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED |
| DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN |
| STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING |
| IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE |
| SUBSTITUTED FOR A KEYED LOCK. |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| MODIFICATION OF THE FIRE ALARM SYSTEM. |
| |