Plan Review Notes
Plan Review Notes For Permit 13051115
Permit Number 13051115
Review Stop B
Sequence Number 2
Notes
Date Text
2013-06-03 15:51:49****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 SEE RAS 117:
  
 1. REVISE SPECIFICATION TO STATE WHETHER THE ROWS
 SPECIFIED INCLUDE OR EXCLUDE THE LAP ROW.
  
 2. ZONE 2 AND ZONE 3, SEE RAS 117 10.4.5, FRACTIONS TO
 BE ROUNDED DOWN TO THE NEXT WHOLE NUMBER.
  
 3. ZONE 3, SEE RAS 117 8.1, MINIMUM FASTENER SEPARATION
 SHALL NOT BE LESS THAN 4 IN. O.C.
  