Plan Review Notes
Plan Review Notes For Permit 13051115
Permit Number 13051115
Review Stop B
Sequence Number 1
Notes
Date Text
2013-06-01 14:11:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. TWO DIFFERENT ASSEMBLIES WERE INCLUDED IN THE NOA
 SUBMITTED. BOTH HAVE GENERAL LIMITATION #9, WHICH DOES
 NOT ALLOW ENHANCED FASTENING. SELECT AN ASSEMBLY WHICH
 EITHER MEETS ZONE 3 (WORST CASE) DESIGN PRESSURES OR
 WHICH INCLLUDES GENERAL LIMITATION #7.
  
 2. IF AN ASSEMBLY WITH GENERAL LIMITATION #7 IS
 SELECTED AND DOES NOT MEET WORST CASE DESIGN PRESSURE,
 RAS 117 CALCULATIONS PREPARED BY AN ARCHITECT,
 ENGINEER, OR REGISTERED ROOF CONSULTANT WILL BE
 REQUIRED. SEE LAST PAGE OF NOA, GENERAL LIMITATION #7,
 AND FBC R 301.
  
  