2013-07-17 16:54:27911 VILLAGE BOULEVARD - SUITE #803
 PERMIT #13051103
 REVIEW #2 COMMENTS - FIRE DEPARTMENT
  
 THE FOLLOWING MEP SHEETS WERE NOT RESUBMITTED FOR
 REVIEW TO ADDRESS THE ORIGINAL PLAN REVIEW COMMENTS:
  
 SHEET 2 AND SHEET E2.1: SHEET 2 INDICATES AN EXTERIOR
 STOREFRONT DOOR TO BE PERMANENTLY SECURED; HOWEVER,
 SHEET E2.1 INDICATES AN EXIT SIGN AT THIS DOOR.
 COORDINATE. IF THIS DOOR IS NOT AN EXIT DOOR, PROVIDE
 PERMANENT OBVIOUS SIGNAGE ON DOOR INDICATING "NOT AN
 EXIT."
  
 SHEET E2.1: NO EXIT SIGN PROVIDED FOR REAR EXIT DOOR.
  
 SHEET M2.1 - DUCT-SOX: THE FLAME SPREAD AND SMOKE
 DEVELOPMENT OF FLEXIBLE AIR DUCTS NEED TO BE LISTED AND
 LABELED AS CLASS 0 OR CLASS 1 PER UL 181. CLASS 0 - AIR
 DUCTS AND AIR CONNECTORS HAVING SURFACE BURNING
 CHARACTERISTICS OF ZERO. CLASS 1 - AIR DUCTS AND AIR
 CONNECTORS HAVING A FLAME-SPREAD INDEX OF NOT OVER 25
 WITHOUT EVIDENCE OF CONTINUED PROGRESSIVE COMBUSTION
 AND A SMOKE-DEVELOPED INDEX OF NOT OVER 50.
  
 SHEET M2.1: VERIFY EXISTING 10 TON AND 7.5 TON UNITS
 ARE EQUIPPED WITH DUCT SMOKE DETECTORS.
  