Plan Review Notes
Plan Review Notes For Permit 13051103
Permit Number 13051103
Review Stop P
Sequence Number 1
Notes
Date Text
2013-06-05 09:30:20FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. IF THE OCCUPANCY TYPE IS A-3, THEN A SERVICE SINK IS
 REQUIRED.
 FBC PLUMBING 2010 TABLE 403.1
  
 2. SHEETS P2.1 & P5.1 IF THE RESTROOM SANITARY IS TWO
 CURCUIT VENT SYSTEMS, A VERTICAL DRY VENT IS REQUIRED
 BETWEEN THE TWO MOST UPSTREAM FLOOR FIXTURES.
 911.2 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved