Plan Review Notes For Permit 13051103 |
Permit Number |
13051103 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-06-05 09:30:20 | FBC 2010 ACCESSIBILITY CODE | | FBC 2010 PLUMBING REVIEW #1 | | DENIED: | | | | 1. IF THE OCCUPANCY TYPE IS A-3, THEN A SERVICE SINK IS | | REQUIRED. | | FBC PLUMBING 2010 TABLE 403.1 | | | | 2. SHEETS P2.1 & P5.1 IF THE RESTROOM SANITARY IS TWO | | CURCUIT VENT SYSTEMS, A VERTICAL DRY VENT IS REQUIRED | | BETWEEN THE TWO MOST UPSTREAM FLOOR FIXTURES. | | 911.2 VENT CONNECTION. | | THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN | | THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL | | CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED | | IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE | | SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. | | | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|