Plan Review Notes
Plan Review Notes For Permit 13051103
Permit Number 13051103
Review Stop B
Sequence Number 1
Notes
Date Text
2013-07-03 17:51:15BUILDING PLAN REVIEW
 PERMIT: 13051103
 ADD: 911 VILLAGE BLVD
 CONT: KARNS & BALDWIN INNOVATIVE BUILDERS
 TEL: (561)805-7528
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 03/2013
 ACTION: DENIED
  
 1) SHEET 1 PLEASE CORRECT OCCUPANCY TYPE TO A-3, 2010
 FBC-B SECTION 303.1.
  
 2) SHEET 2 INDICATES THE USE OF CLOSED CELL ICYENE R-8
 INSULATION APPLIED TO THE BOTTOM OF THE BAR JOIST.
 PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION FOR
 ICYENE PROVIDING HOW THICK THE INSULATION WILL NEED TO
 BE APPLIED TO ACHIEVE A R-8 VALUE.
 2A) PROVIDE PRODUCT COMPLIANCE FOR:
 FBC-B 2603.5.2 THERMAL BARRIER. ANY FOAM PLASTIC
 INSULATION SHALL BE SEPARATED FROM THE BUILDING
 INTERIOR BY A THERMAL BARRIER MEETING THE PROVISIONS OF
 SECTION 2603.4, UNLESS SPECIAL APPROVAL IS OBTAINED ON
 THE BASIS OF SECTION 2603.9.
  
 FBC-B 2603.9 SPECIAL APPROVAL.
 FOAM PLASTIC SHALL NOT BE REQUIRED TO COMPLY WITH THE
 REQUIREMENTS OF SECTIONS 2603.4 THROUGH 2603.7 WHERE
 SPECIFICALLY APPROVED BASED ON LARGE-SCALE TESTS SUCH
 AS, BUT NOT LIMITED TO, NFPA 286 (WITH THE
 ACCEPTANCE CRITERIA OF SECTION 803.2), FM 4880, UL 1040
 OR UL 1715. SUCH TESTING SHALL BE RELATED TO THE ACTUAL
 END-USE CONFIGURATION AND BE PERFORMED ON THE FINISHED
 MANUFACTURED FOAM PLASTIC
 ASSEMBLY IN THE MAXIMUM THICKNESS INTENDED FOR USE.
 FOAM PLASTICS THAT ARE USED AS INTERIOR FINISH ON THE
 BASIS OF SPECIAL TESTS SHALL ALSO CONFORM TO THE FLAME
 SPREAD REQUIREMENTS OF CHAPTER 8. ASSEMBLIES
 TESTED SHALL INCLUDE SEAMS, JOINTS AND OTHER TYPICAL
 DETAILS USED IN THE INSTALLATION OF THE ASSEMBLY AND
 SHALL BE TESTED IN THE MANNER INTENDED FOR USE.
  
 2B) 2603.7 PLENUMS. FOAM PLASTIC INSULATION SHALL NOT
 BE USED AS INTERIOR WALL OR CEILING FINISH IN PLENUMS
 EXCEPT AS PERMITTED IN SECTION 2604 OR WHEN PROTECTED
 BY A THERMAL BARRIER IN ACCORDANCE WITH SECTION 2603.4.
  
 2C) DEPENDING ON THE METHOD OF APPLICATION THIS CODE
 SECTION MAY ALSO HAVE SOME REVEVANCE, ONCE THE
 MANUFACTURERS SPECS AND TYPE OF APPLICATION IS KNOWN.
 2603.4.1.6 ATTICS AND CRAWL SPACES.
 WITHIN AN ATTIC OR CRAWL SPACE WHERE ENTRY IS MADE ONLY
 FOR SERVICE OF UTILITIES, FOAM PLASTIC INSULATION SHALL
 BE PROTECTED AGAINST IGNITION BY 11/2-INCH-THICK (38
 MM) MINERAL FIBER INSULATION; 1/4-INCH-THICK (6.4 MM)
 WOOD STRUCTURAL PANEL, PARTICLEBOARD OR HARDBOARD;
 3/8-INCH (9.5 MM) GYPSUM WALLBOARD, CORROSION-RESISTANT
 STEEL HAVING A BASE METAL THICKNESS OF 0.016 INCH (0.4
 MM) OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A
 MANNER THAT THE FOAM PLASTIC INSULATION IS NOT EXPOSED.
 THE PROTECTIVE COVERING SHALL BE CONSISTENT WITH THE
 REQUIREMENTS FOR THE TYPE OF CONSTRUCTION.
  
 3) SHEET 2 SHOWS A 42 INCH HIGH JUICE BAR, PLEASE
 PROVIDE HOW COMPLIANCE WITH SECTION 2010 FBC-B 902.3
 HEIGHT. THE TOPS OF DINING SURFACES AND WORK SURFACES
 SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676