Plan Review Notes
Plan Review Notes For Permit 13051101
Permit Number 13051101
Review Stop B
Sequence Number 2
Notes
Date Text
2013-06-07 16:46:12****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. THE ASSEMBLY SELECTED, W15 ON PAGE 6, DOES NOT MEET
 DESIGN PRESSURE REQUREMENTS FOR THIS ZONE 3 FOR THIS
 JOB. ZONE 3 EXPOSURE D REQUIRES -116.2. MINIMUM FBC R
 TABLE 301.2(2) AND (3).
  
 THE ASSEMBLY SELECTED HAS A LIMITATION OF -90 PSF.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved