Plan Review Notes For Permit 13051101 |
Permit Number |
13051101 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-06-07 16:46:12 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. THE ASSEMBLY SELECTED, W15 ON PAGE 6, DOES NOT MEET | | DESIGN PRESSURE REQUREMENTS FOR THIS ZONE 3 FOR THIS | | JOB. ZONE 3 EXPOSURE D REQUIRES -116.2. MINIMUM FBC R | | TABLE 301.2(2) AND (3). | | | | THE ASSEMBLY SELECTED HAS A LIMITATION OF -90 PSF. | | |
|