2013-06-01 14:24:08****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE ASSEMBLY SELECTED HAS A DESIGN PRESSURE
 LIMITATION OF -67.5. AS MEAN ROOF HEIGHT WAS NOT
 PROVIDED, IT CANNOT BE DETERMINED WHETHER OR NOT THIS
 COMPLIES FOR ZONE 2. HOWEVER, THIS DOES NOT COMPLY FOR
 ZONE 3.
  
 SEE GENERAL LIMITATION #7, RAS 117 CALCULATIONS TO BE
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT, FBC R 301.
  