2013-06-18 12:37:09 | 700 NORTHPOINT PARKWAY - SUITE #200 | | PERMIT #13051096 | | MASTER #13030378 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PLANS HAVE BEEN APPROVED WITH THE FOLLOWING | | PROVISIONS:***** | | | | SECURITY DEVICES (CARD READERS, TV, ETC.) SHALL NOT BE | | LOCATED IN THE STAIRS PER NFPA 101 | | SECTION7.1.3.2.1(10)(B): PENETRATIONS FOR ELECTRICAL | | WIRING ARE PERMITTED WHERE THE WIRING SERVES EQUIPMENT | | PERMITTED BY THE AUTHORITY HAVING JURISDICTION TO BE | | LOCATED WITHIN THE EXIT ENCLOSURE, SUCH AS SECURITY | | SYSTEMS, PUBLIC ADDRESS SYSTEMS, AND FIRE DEPARTMENT | | EMERGENCY COMMUNICATIONS DEVICES. | | | | MAGNETIC LOCKS: | | - ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL | | AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF | | EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE | | FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET. | | - ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER SYSTEM | | OR AUTOMATIC DETECTION SYSTEM SHALL AUTOMATICALLY | | UNLOCK THE DOORS IN THE DIRECTION OF EGRESS, AND THE | | DOORS SHALL REMAIN UNLOCKED UNTIL THE FIRE ALARM SYSTEM | | HAS BEEN MANUALLY RESET. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|