2013-06-14 16:14:53 | BUILDING PLAN REVIEW |
| PERMIT: 13051060 |
| ADD: 2101 CENTREPARK BLVD # 110 |
| CONT: CHANDLER CONSTRUCTION |
| TEL: (561)791-6934 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: 6/14/2013 |
| ACTION: DENIED |
| |
| 1) THE PROJECT DATA DOES NOT INDICATE THE BUILDING IS |
| FIRE SPRINKLERED, SHEET A-3.0 THE FIRE SPRINKLER HEAD |
| PLAN IS LOCATED. HAVING THE FIRE SPRINKLER DESIGNATION |
| IN THE PROJECT DATA SETS UP THE PERIMETERS THE PLAN |
| REVIEW WILL OCCUR UNDER. |
| |
| 2) SHEET A-1 INDICATES WITHIN THE BUSINESS OCCUPANCY |
| THERE IS LOCATED TWO CONFERENCE ROOMS THE TOTAL SQ FEET |
| OF THESE COMBINED AREA IS 1154 SQ FT. TO CONSIDER THIS |
| AREA AS A ACCESSORY OCCUPANCY THROUGH THE FBC-B |
| 508.2.1, AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT |
| OCCUPY MORE THAN 10 PERCENT OF THE BUILDING AREA OF THE |
| STORY IN WHICH THEY ARE LOCATED AND SHALL NOT EXCEED |
| THE TABULAR VALUES IN TABLE 503, WITHOUT BUILDING AREA |
| INCREASES IN ACCORDANCE WITH SECTION 506 FOR SUCH |
| ACCESSORY OCCUPANCIES. |
| |
| THE TOTAL FLOOR AREA, FOOT PRINT OF THIS BUILDING IS |
| 25,272 SQ FT THE DESIGNER OF RECORD CAN PROVIDE |
| DOCUMENTATION THAT THE TOTAL SQ FOOTAGE OF COMBINED |
| TENANTS CONFERENCE ROOMS DOES NOT EXCEED THE 10% OF THE |
| BUILDING AREA THEN THIS CAN BE CONSIDERED A ACCESSORY |
| OCCUPANCY. |
| |
| 3) SHEET A-3 DOES INDICATE THIS BUILDING IS A |
| SPRINKLERED BUILDING, ONE OF THE EXCEPTIONS TO MANUAL |
| FIRE ALARM BOXES IN FIRE SPRINKLERED BUILDINGS IS FOUND |
| IN 2010 FBC-B 907.2.2 FOR GROUP B OCCUPANCIES, BUT |
| PLEASE NOTE FBC-B 907.2. WHERE OTHER SECTIONS OF THIS |
| CODE ALLOW ELIMINATION OF FIRE ALARM BOXES DUE TO |
| SPRINKLERS, A SINGLE FIRE ALARM BOX SHALL BE INSTALLED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |