2013-05-30 17:46:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. IF
 NON COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED
 CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%.
  
 2. FOR THE SHUTTERS, COMPLETE THE SAMPLE INSTALLATION
 SCHEDULE OR PROVIDE ALL INFORMATION TO SHOW CODE
 COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC R301,
 FBC1609. TWO SETS REQUIRED. THIS FORM IS AVAILABLE IN
 THE LOBBY OR ON THE INTERNET AT:
  
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
 INCLUDE THE ROOM DESIGNATION.
  