Plan Review Notes
Plan Review Notes For Permit 13050894
Permit Number 13050894
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-06-19 12:58:093620 S. DIXIE HWY, BUILDING 2
 PERMIT #13050894
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 1. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK
 INFORMATION.
 2. SHEET E-1.2: SHOW COMBINATION CO/SMOKE ALARM OUTSIDE
 GARAGE DOOR FOR RETAIL/OFFICE FLOOR PLAN AS SHOWN IN
 PRIOR FLOOR PLANS.
 3. UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION
 OF THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
 4. ALL CONSTRUCTION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
 5. PROVIDE BUILDING AND UNIT ADDRESSES VISIBLE FROM THE
 STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND
 BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND
 SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION
 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA
 1).
 6. STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER "RF"
 (ROOF-FLOOR) DESIGNATION PER FLORIDA STATUTE 633.027
 AND FLORIDA ADMINISTRATIVE CODE 69A-60.0081.
 7. SHEET A-1UA: DOORS SUCH AS #9 SHOULD HAVE A FIRE
 RESISTANCE RATING OF 90 MINUTES WHEN LOCATED WITHIN A
 2-HOUR FIRE BARRIER.
 8. COMMERCIAL SPACE: PROVIDE PORTABLE FIRE
 EXTINGUISHERS. EXTINGUISHERS SHALL HAVE A MINIMUM
 RATING OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED
 FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO
 EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 9. FIRE SPRINKLER: INDICATE THE LOCATION OF THE FIRE
 DEPARTMENT CONNECTION.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  