Date Text
2013-06-18 16:02:13****PROVISO****
 1. 424.1.6.5.3.2.3 EQUALIZERS.
 RECESSED AUTOMATIC SURFACE SKIMMERS SHALL BE INSTALLED
 WITH AN EQUALIZER VALVE AND AN EQUALIZER LINE WHEN THE
 SKIMMER PIPING SYSTEM IS CONNECTED DIRECTLY TO PUMP
 SUCTION. IF INSTALLED, THE EQUALIZER VALVE SHALL BE A
 SPRING LOADED VERTICAL CHECK VALVE WHICH WILL NOT ALLOW
 DIRECT SUCTION ON THE EQUALIZER LINE. FLOAT VALVES ARE
 PROHIBITED. THE EQUALIZER LINE INLET SHALL BE INSTALLED
 AT LEAST 1 FOOT (305 MM) BELOW THE NORMAL POOL WATER
 LEVEL AND THE EQUALIZER LINE INLET SHALL BE PROTECTED
 BY AN ASME/ANSI A112.19.8 COMPLIANT COVER/GRATE. THE
 EQUALIZER LINE SHALL BE SIZED TO HANDLE THE EXPECTED
 FLOW WITH A 2-INCH (51 MM) MINIMUM LINE SIZE.
  
 2. POOL WASTE SHALL BE TO SANITARY SEWER PER SEC.
 90-203. - PROHIBITED DISCHARGES; ILLICIT CONNECTIONS.
 (A)
 GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION
 90-205, AND EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR
 INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY
 OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER
 SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT
 COMPOSED ENTIRELY OF STORMWATER.
  
  