2013-06-07 09:02:50 | 1751 PALM BEACH LAKES BOULEVARD - PB MALL BUILDING J-5 |
| PERMIT #13050878 |
| MASTER #12110060 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| *****PROVISO - SUBMIT REVISION***** |
| |
| FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED |
| SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. |
| |
| PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| CONNECTION. |
| |
| PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE |
| DEPARTMENT CONNECTION. |
| |
| PROVIDE 4 SIDEWALL SPRINKLERS NEAR THE TOP OF THE SHADE |
| CANOPIES. |
| |
| SHEET FP-1 "FIRE PROTECTION NOTE #5": RETAIL SHOULD BE |
| DESIGNED TO ORDINARY HAZARD GROUP 2 @ 0.20 GPM/SQ.FT. |
| DENSITY TO THE MATCH THE HYDRAULIC CALCULATIONS. |
| |
| HYDRAULIC CALCULATIONS INDICATE THE CROSS MAIN FOR |
| NODES L1 THROUGH L36 TO BE SIZED AT 2-1/2"; HOWEVER, |
| THE PLANS SHOW THIS CROSS MAIN TO SIZED AT 4". |
| COORDINATE PIPE SIZING. |
| |
| SHEET FP-3: THE LIGHT HAZARD OFFICE HYDRAULIC |
| CALCULATION HAS THE LONG SIDE (1.2 X THE SQUARE ROOT OF |
| THE AREA OF SPRINKLER OPERATION) OF THE HYDRAULIC AREA |
| DRAWN PERPENDICULAR TO THE BRANCH LINES WHEN THE LONG |
| SIDE OF THE HYDRAULIC AREA SHOWN BE RUN PARALLEL TO THE |
| BRANCH LINES PER NFPA 13 (2010 EDITION) SECTION |
| 22.4.4.1.1.1. REVISE DRAWING AND HYDRAULIC |
| CALCULATIONS. |
| |
| WESLEY JOLIN |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |