 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 PROVIDE 4 SIDEWALL SPRINKLERS NEAR THE TOP OF THE SHADE
 CANOPIES.
  
 SHEET FP-1 "FIRE PROTECTION NOTE #5": RETAIL SHOULD BE
 DESIGNED TO ORDINARY HAZARD GROUP 2 @ 0.20 GPM/SQ.FT.
 DENSITY TO THE MATCH THE HYDRAULIC CALCULATIONS.
  
 HYDRAULIC CALCULATIONS INDICATE THE CROSS MAIN FOR
 NODES L1 THROUGH L36 TO BE SIZED AT 2-1/2"; HOWEVER,
 THE PLANS SHOW THIS CROSS MAIN TO SIZED AT 4".
 COORDINATE PIPE SIZING.
  
 SHEET FP-3: THE LIGHT HAZARD OFFICE HYDRAULIC
 CALCULATION HAS THE LONG SIDE (1.2 X THE SQUARE ROOT OF
 THE AREA OF SPRINKLER OPERATION) OF THE HYDRAULIC AREA
 DRAWN PERPENDICULAR TO THE BRANCH LINES WHEN THE LONG
 SIDE OF THE HYDRAULIC AREA SHOWN BE RUN PARALLEL TO THE
 BRANCH LINES PER NFPA 13 (2010 EDITION) SECTION
 22.4.4.1.1.1. REVISE DRAWING AND HYDRAULIC
 CALCULATIONS.
  