2013-06-13 13:34:06 | BUILDING PROVISO: | | PROVIDE CODE COMPLIANCE FOR 2010 FBC-B 1008.1.9.8 | | ELECTROMAGNETICALLY LOCKED EGRESS DOORS. | | DOORS TO TENANT SPACES IN GROUP B SHALL BE PERMITTED TO | | BE ELECTROMAGNETICALLY LOCKED IF EQUIPPED WITH LISTED | | HARDWARE THAT | | INCORPORATES A BUILT-IN SWITCH AND MEET THE | | REQUIREMENTS BELOW: | | | | 1. THE LISTED HARDWARE THAT IS AFFIXED TO THE DOOR LEAF | | HAS AN OBVIOUS METHOD OF OPERATION THAT IS READILY | | OPERATED UNDER ALL LIGHTING CONDITIONS. | | | | 2. THE LISTED HARDWARE IS CAPABLE OF BEING OPERATED | | WITH ONE HAND. | | | | 3. OPERATION OF THE LISTED HARDWARE RELEASES TO THE | | ELECTROMAGNETIC LOCK AND UNLOCKS THE DOOR IMMEDIATELY. | | | | 4. LOSS OF POWER TO THE LISTED HARDWARE AUTOMATICALLY | | UNLOCKS THE DOOR. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|