Plan Review Notes
Plan Review Notes For Permit 13050781
Permit Number 13050781
Review Stop E
Sequence Number 1
Notes
Date Text
2013-06-19 15:07:08PERMIT ISSUED WITH THE FOLLOWING PROVISO:
  
 1. COMMERCIAL EQUIPMENT LIKELY TO BE SERVICE WHILE
 ENERGIZED MUST HAVE SAFETY WARNING LABEL TO PROTECT
 FROM ARC FLASH HAZARD PER NES 110.16
 2. CONFERENCE ROOM FLOOR BOX CONDUCTORS MUST BE RATED
 FOR WET LOCATION PER NEC 300.5B
 3. AC EQUIPMENT SCHEDULE ON DRAWING A4 SHOWS CU'S TO
 HAVE MOCP OF 30/2. PANEL A SHOWS 50/2 AND PANEL B SHOWS
 4-/2. PEASE REVISE
 4. AC EQUIPMENT SCHEDULE ON DRAWING A4 SHOWS AHU#2 TO
 HAVE MOCP OF 40/2. PANEL B SHOWS 50/2. PLEASE REVISE.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6718
  