Plan Review Notes For Permit 13050779 |
Permit Number |
13050779 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-06-19 15:32:26 | PERMIT ISSUED WITH THE FOLLOWING PROVISO: | | | | 1. COMMERCIAL EQUIPMENT LIKELY TO BE SERVICE WHILE | | ENERGIZED MUST HAVE SAFETY WARNING LABEL TO PROTECT | | FROM ARC FLASH HAZARD PER NEC 110.16 | | 2. CONFERENCE ROOM FLOOR BOX CONDUCTORS MUST BE RATED | | FOR WET LOCATION PER NEC 300.5B | | 3. AC EQUIPMENT SCHEDULE ON DRAWING A4 SHOWS CU'S TO | | HAVE MOCP OF 30/2. PANEL A SHOWS 50/2 AND PANEL B SHOWS | | 4-/2. PEASE REVISE | | 4. AC EQUIPMENT SCHEDULE ON DRAWING A4 SHOWS AHU#2 TO | | HAVE MOCP OF 40/2. PANEL B SHOWS 50/2. PLEASE REVISE. | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | 561-805-6718 | | |
|