2013-09-18 08:55:15 | BUILDING PLAN REVIEW |
| PERMIT:13050770 |
| ADD: MASTER PLAN NEW & MODIFIED TROLLEY SHELTERS |
| CONT: TBD |
| CONTACT: VIVEK GALAV |
| TEL: (561)494-1061 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: SEPT 18/ 2013 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. THE MODIFIED AND NEW TROLLEY SHELTERS |
| ARE GOING TO BE MASTERED WE WILL NEED THE SHOP DRAWINGS |
| THAT PROVIDE THE FASTENING DETAILS FOR ALL OF THE |
| FRAMING MEMBERS. THE 700 SERIES OF SHEETS INDICATE ALL |
| CONNECTIONS ARE TO BE WELDED OR CONCEALED FASTENERS |
| SHOP DRAWING ARE TO INCLUDE ALL CONNECTION METHODS FOR |
| ARCHIETECT REVIEW. 2010 WPB ADMINISTRATIVE CODE, |
| CHAPTER 1 ADMINISTRATION, 2010 EDITION.107.3.5.1.1(8) |
| MINIMUM PLAN REVIEW CRITERIA COMMERCIAL BUILDINGS, |
| STRUCTURAL. |
| |
| 2) PROVISO: NOT PART OF THIS PERMIT. SHEET A2.02 ROOF |
| PLANS FOR NEW AND RENOVATED SHELTERS ALSO INDICATES THE |
| USE OF SOLAR PHOTOVOLTIAC SYSTEMS, PLEASE NOTE THIS |
| SYSTEM WILL REQUIRE A SEPERATE ELECTRICAL PERMIT AND |
| ASSOCIATED FEES. PLEASE BACK OUT THE VALUE FOR THIS |
| SYSTEM OUT OF THE BUILDING COST TO BE COVERED UNDER THE |
| PHOTOVOLTIAC ELECTRIC PERMIT. 109.3 WPB ADMINISTRATIVE |
| CODE, BUILDING PERMIT VALUATION. |
| |
| 3) 2ND REQUEST. SHEET A2.02 IN THE ROOFING NOTES |
| DESCRIBES A ROOFING SYSTEM, KEMPEROL 2K-PUR: FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) (D) ROOFING PRODUCTS AND ASSEMBLIES PLEASE |
| SUBMIT 2 COPIES OF PRODUCT APPROVAL, PLEASE CIRCLE THE |
| SYSTEM THAT WILL BE ATTACHED TO ALUMINUM TUBING/ DECK |
| AS DEPICTED ON A2.02. A ENGINEER MAY DO RATIONAL |
| ANYLSIS IF THE PRODUCT WAS TESTED ON A STEEL DECK TO |
| THE ALUMINUM DECK/ TUBING. |
| |
| 4) COMPLIED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |