Plan Review Notes
Plan Review Notes For Permit 13050770
Permit Number 13050770
Review Stop B
Sequence Number 1
Notes
Date Text
2013-06-03 14:26:18BUILDING PLAN REVIEW
 PERMIT:13050770
 ADD: MASTER PLAN NEW & MODIFIED TROLLEY SHELTERS
 CONT: TBD
 CONTACT: VIVEK GALAV
 TEL: (561)494-1061
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JUNE 03/ 2013
 ACTION: DENIED
  
 1) THE MODIFIED AND NEW TROLLEY SHELTERS ARE GOING TO
 BE MASTERED WE WILL NEED THE SHOP DRAWINGS THAT PROVIDE
 THE FASTENING DETAILS FOR ALL OF THE FRAMING MEMBERS.
 THE 700 SERIES OF SHEETS INDICATE ALL CONNECTIONS ARE
 TO BE WELDED OR CONCEALED FASTENERS SHOP DRAWING ARE TO
 INCLUDE ALL CONNECTION METHODS FOR ARCHIETECT REVIEW.
 2010 WPB ADMINISTRATIVE CODE, CHAPTER 1 ADMINISTRATION,
 2010 EDITION.107.3.5.1.1(8) MINIMUM PLAN REVIEW
 CRITERIA COMMERCIAL BUILDINGS, STRUCTURAL.
  
 2) SHEET A2.02 ROOF PLANS FOR NEW AND RENOVATED
 SHELTERS ALSO INDICATES THE USE OF SOLAR PHOTOVOLTIAC
 SYSTEMS, PLEASE NOTE THIS SYSTEM WILL REQUIRE A
 SEPERATE ELECTRICAL PERMIT AND ASSOCIATED FEES. PLEASE
 BACK OUT THE VALUE FOR THIS SYSTEM OUT OF THE BUILDING
 COST TO BE COVERED UNDER THE PHOTOVOLTIAC ELECTRIC
 PERMIT. 109.3 WPB ADMINISTRATIVE CODE, BUILDING PERMIT
 VALUATION.
  
 3) SHEET A2.02 IN THE ROOFING NOTES DESCRIBES A ROOFING
 SYSTEM, KEMPEROL 2K-PUR: FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) (D) ROOFING PRODUCTS AND ASSEMBLIES PLEASE
 SUBMIT 2 COPIES OF PRODUCT APPROVAL, PLEASE CIRCLE THE
 SYSTEM THAT WILL BE ATTACHED TO ALUMINUM TUBING/ DECK
 AS DEPICTED ON A2.02. A ENGINEER MAY DO RATIONAL
 ANYLSIS IF THE PRODUCT WAS TESTED ON A STEEL DECK TO
 THE ALUMINUM DECK/ TUBING.
  
 4) SHEET S1.0 INDICATES THE STRUCTURES WERE DESIGNED TO
 A "C" EXPOSURE, THE WORST CASE EXPOSURE OCCURS @ DATURA
 & FLAGLER A EXPOSURE D LOCATION.
 1609.4.3 EXPOSURE CATEGORIES. EXPOSURE D. EXPOSURE D
 SHALL APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS
 DEFINED BY SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND
 DIRECTION FOR A DISTANCE OF AT LEAST 5,000 FEET (1524
 M) OR 20 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS
 GREATER. EXPOSURE D SHALL EXTEND INLAND FROM THE
 SHORELINE FOR A DISTANCE OF 600 FEET (183 M) OR 20
 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER
 FROM AN EXPOSURE D CONDITION AS DEFINED IN THE PREVIOUS
 SENTENCE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  