2013-06-03 14:26:18 | BUILDING PLAN REVIEW |
| PERMIT:13050770 |
| ADD: MASTER PLAN NEW & MODIFIED TROLLEY SHELTERS |
| CONT: TBD |
| CONTACT: VIVEK GALAV |
| TEL: (561)494-1061 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: JUNE 03/ 2013 |
| ACTION: DENIED |
| |
| 1) THE MODIFIED AND NEW TROLLEY SHELTERS ARE GOING TO |
| BE MASTERED WE WILL NEED THE SHOP DRAWINGS THAT PROVIDE |
| THE FASTENING DETAILS FOR ALL OF THE FRAMING MEMBERS. |
| THE 700 SERIES OF SHEETS INDICATE ALL CONNECTIONS ARE |
| TO BE WELDED OR CONCEALED FASTENERS SHOP DRAWING ARE TO |
| INCLUDE ALL CONNECTION METHODS FOR ARCHIETECT REVIEW. |
| 2010 WPB ADMINISTRATIVE CODE, CHAPTER 1 ADMINISTRATION, |
| 2010 EDITION.107.3.5.1.1(8) MINIMUM PLAN REVIEW |
| CRITERIA COMMERCIAL BUILDINGS, STRUCTURAL. |
| |
| 2) SHEET A2.02 ROOF PLANS FOR NEW AND RENOVATED |
| SHELTERS ALSO INDICATES THE USE OF SOLAR PHOTOVOLTIAC |
| SYSTEMS, PLEASE NOTE THIS SYSTEM WILL REQUIRE A |
| SEPERATE ELECTRICAL PERMIT AND ASSOCIATED FEES. PLEASE |
| BACK OUT THE VALUE FOR THIS SYSTEM OUT OF THE BUILDING |
| COST TO BE COVERED UNDER THE PHOTOVOLTIAC ELECTRIC |
| PERMIT. 109.3 WPB ADMINISTRATIVE CODE, BUILDING PERMIT |
| VALUATION. |
| |
| 3) SHEET A2.02 IN THE ROOFING NOTES DESCRIBES A ROOFING |
| SYSTEM, KEMPEROL 2K-PUR: FLORIDA DEPARTMENT OF |
| COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) (D) ROOFING PRODUCTS AND ASSEMBLIES PLEASE |
| SUBMIT 2 COPIES OF PRODUCT APPROVAL, PLEASE CIRCLE THE |
| SYSTEM THAT WILL BE ATTACHED TO ALUMINUM TUBING/ DECK |
| AS DEPICTED ON A2.02. A ENGINEER MAY DO RATIONAL |
| ANYLSIS IF THE PRODUCT WAS TESTED ON A STEEL DECK TO |
| THE ALUMINUM DECK/ TUBING. |
| |
| 4) SHEET S1.0 INDICATES THE STRUCTURES WERE DESIGNED TO |
| A "C" EXPOSURE, THE WORST CASE EXPOSURE OCCURS @ DATURA |
| & FLAGLER A EXPOSURE D LOCATION. |
| 1609.4.3 EXPOSURE CATEGORIES. EXPOSURE D. EXPOSURE D |
| SHALL APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS |
| DEFINED BY SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND |
| DIRECTION FOR A DISTANCE OF AT LEAST 5,000 FEET (1524 |
| M) OR 20 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS |
| GREATER. EXPOSURE D SHALL EXTEND INLAND FROM THE |
| SHORELINE FOR A DISTANCE OF 600 FEET (183 M) OR 20 |
| TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER |
| FROM AN EXPOSURE D CONDITION AS DEFINED IN THE PREVIOUS |
| SENTENCE. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |