2013-05-29 15:35:44 | FBC 2010 EXISTING BUILDING CODE |
| FBC 2010 ACCESSIBILITY CODE |
| FBC 2010 PLUMBING REVIEW #1 |
| DENIED: |
| |
| 1. SHEET P-8: THE WATER CLOSETS ON THE 3RD FLOOR |
| ISOMETRIC ARE NOT VENTED. |
| 901.2.1 VENTING REQUIRED. |
| EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN |
| ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN |
| THIS CHAPTER. |
| |
| 2. SHEET P-8: THREE WATER CLOSETS ARE NOT VENTED ON THE |
| 1ST FLOOR. IF THE FIRST FLOOR RESTROOMS ARE A CIRCUIT |
| VENT, A VERTICAL DRY VENT IS REQUIRED BETWEEN THE TWO |
| MOST UPSTREAM WATER CLOSETS. |
| 911.2 VENT CONNECTION. |
| THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN |
| THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL |
| CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED |
| IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE |
| SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. |
| |
| 3. SHEET P-8: AS SHOWN, THE TWO WATER CLOSETS FOR ROOMS |
| 118 & 108 ARE VENTED WITH A HORIZONTAL DRY VENT. |
| 905.4 VERTICAL RISE OF VENT. |
| EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6 |
| INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE |
| HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| |
| 4. PLEASE PROVIDE PIPE SIZES FOR ROOF DRAINAGE SHOWN ON |
| P-2 THROUGH P-5 PER TABLE 1106.2(1) & 1106.3 |
| |
| 5. A HI/LO DRINKING FOUNTAIN WILL BE REQUIRED ON THE |
| 1ST FLOOR PER PLUMBING TABLE 403.1 AND FBC |
| ACCESSIBILITY 211.1 GENERAL. |
| WHERE DRINKING FOUNTAINS ARE PROVIDED ON AN EXTERIOR |
| SITE, ON A FLOOR, OR WITHIN A SECURED AREA THEY SHALL |
| BE PROVIDED IN ACCORDANCE WITH 211. |
| |
| 211.2 MINIMUM NUMBER. |
| NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| |
| REVIEW BY |
| LARRY WAGNER |
| CHIEF PLUMBING INSPECTOR |
| PHONE # 805-6692 |
| EMAIL [email protected] |
| FAX # 805-6676 |
| |
| |
| |