2013-06-04 14:41:40PLANS DENIED
 1) PROVIDE DUCT SIZE ON ALL DUCT.
 PER SECTION 107 FBC 2010
 2) PROVIDE A DETAIL ON CONDENSER STAND TIED TO ROOF
 IF NOT EXISTING . PROVIDE A DETAIL ON CONDENSER TIED TO
 STAND.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER