2013-06-05 13:08:26 | 313 DATURA STREET |
| PERMIT #13050713 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101 |
| REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION |
| WITH FLORIDA AMENDMENTS.) |
| |
| GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE |
| BUILDING ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL |
| BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES |
| IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| BACKGROUND. |
| |
| GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| ORDERED FROM WWW.KNOXBOX.COM. |
| |
| GENERAL - ELEVATOR RECALL: PER SECTION 9.4.3.2, ALL |
| EXISTING ELEVATORS HAVING A TRAVEL DISTANCE OF 25 FEET |
| OR MORE ABOVE OR BELOW THE LEVEL THAT BEST SERVES THE |
| NEEDS OF EMERGENCY PERSONNEL FOR FIRE-FIGHTING OR |
| RESCUE PURPOSES SHALL CONFORM TO THE FIRE FIGHTERS. |
| EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.3, SAFETY |
| CODE FOR EXISTING ELEVATORS AND ESCALATORS. |
| |
| SHEET LS-01: UPDATE THE CODE LIST TO REFERENCE THE 2010 |
| EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| WITH FLORIDA AMENDMENTS. |
| |
| SHEET LS-01 - EXISTING STAIR #1: PER SECTION 7.2.2.5.3, |
| ENCLOSED, USABLE SPACES WITHIN EXIT ENCLOSURES SHALL BE |
| PROHIBITED, INCLUDING UNDER STAIRS, UNLESS THE SPACE |
| UNDER THE STAIRS MEETS THE FOLLOWING REQUIREMENTS: |
| (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR |
| ENCLOSURE BY THE SAME FIRE RESISTANCE AS THE EXIT |
| ENCLOSURE. |
| (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE |
| FROM WITHIN THE STAIR ENCLOSURE. |
| (3) THE SPACE IS NOT USED FOR THE STORAGE OF FLAMMABLE |
| OR OTHERWISE HAZARDOUS MATERIALS. |
| |
| SHEET LS-02: EXISTING STAIR #1 (SECOND FLOOR) INDICATES |
| OCCUPANTS FROM THE THIRD FLOOR MUST EXIT THE PROTECTED |
| STAIR ENCLOSURE AND THEN RE-ENTER THE PROTECTED STAIR |
| ENCLOSURE TO EXIT THE BUILDING. SECTION 7.1.3.2.2 |
| REQUIRES AN EXIT ENCLOSURE TO PROVIDE A CONTINUOUS |
| PROTECTED PATH OF TRAVEL TO AN EXIT DISCHARGE. THIS |
| APPLIES TO NEW AND EXISTING CONDITIONS PER NFPA 1 |
| SECTIONS 14.3.2 AND 1.3.1. |
| |
| GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| DOORS WITH EXIT SIGNS. |
| |
| GENERAL: PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL |
| BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING |
| READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| FEET ON CENTER. |
| |
| SHEET E1.1-1.3: PROVIDE EMERGENCY LIGHTING FOR EXTERIOR |
| STAIRS AND EXTERIOR ROOF EGRESS PATH LEADING TO THE |
| EXIT DISCHARGE (ALLEY). EMERGENCY ILLUMINATION SHALL BE |
| PROVIDED FOR A MINIMUM OF .5 HOURS IN THE EVENT OF |
| FAILURE OF NORMAL LIGHTING. EMERGENCY LIGHTING |
| FACILITIES SHALL BE ARRANGED TO PROVIDE INITIAL |
| ILLUMINATION THAT IS NOT LESS THAN AN AVERAGE OF 1 |
| FT-CANDLE AND, AT ANY POINT, NOT LESS THAN 0.1 |
| FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT FLOOR |
| LEVEL. |
| |
| SHEET FA-1: NO FIRE ALARM NOTIFICATION APPLIANCES |
| PROVIDED IN TOILET #118, TOILET #112, TOILET #113, |
| OFFICE SPACE #111, OR CORRIDOR #103. |
| |
| SHEET FA-1: FIRE ALARM SYSTEM SHALL BE FULLY |
| ADDRESSABLE. |
| |
| ELECTRICAL: PLANS DO NOT INDICATE THE METHOD (HEAT |
| DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT |
| TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC |
| SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM. |
| |
| FIRE SPRINKLER: THE RETAIL (MERCANTILE OCCUPANCY) |
| SHOULD BE DESIGN FOR ORDINARY HAZARD GROUP 1 OR GROUP 2 |
| IN LIEU OF THE LIGHT HAZARD DESIGNATION INDICATED ON |
| THE PLAN. |
| |
| FIRE SPRINKLER: PROVIDE CURRENT HYDRANT FLOW TEST |
| INFORMATION ON THE PLANS. |
| |
| FIRE SPRINKLER: REGULAR STANDARD SPRAY SPRINKLERS ARE |
| NO LONGER AN ACCEPTABLE METHOD FOR PROTECTING GLAZING |
| TO ACHEIVE A 1-HOUR FIRE RATED SEPARATION. CURRENTLY, |
| ONLY TYCO "WINDOW SPRINKLERS" ARE LISTED TO ACHIEVE A |
| ONE-HOUR OR TWO-HOUR FIRE RATED EQUIVALENT FOR |
| PROTECTING GLAZING ASSEMBLIES. |
| |
| TYCO WINDOW SPRINKLERS: IF THE DESIGN INTENT IS TO USE |
| TYCO WINDOW SPRINKLERS (IN LIEU OF FIRE-RATED GLASS) TO |
| ACHIEVE A FIRE RATED SEPARATION, THE SPRINKLERS MUST BE |
| INSTALLED ACCORDING TO THE UL LISTING DATA AND SHALL |
| WET THE ENTIRE GLAZING SURFACE. SPRINKLERS CANNOT BE |
| USED TO PROTECT OPERABLE DOORS OR WINDOWS. THE WINDOW |
| SPRINKLERS DO NOT ALLOW HORIZONTAL WINDOW MULLIONS AND |
| REQUIRE THE GLASS CURTAIN WALL TO BE ATTACHED TO A |
| THREE FOOT HIGH PONY WALL TO KEEP COMBUSTIBLE MATERIALS |
| AT LEAST TWO INCHES AWAY FROM THE GLAZING. PAY SPECIAL |
| ATTENTION TO THE GLAZING ASSEMBLY AS THE SPRINKLER |
| POSITIONING VARIES FOR BUTT-GLAZED INSTALLATIONS |
| COMPARED TO VERTICAL MULLION INSTALLATIONS. VERTICAL |
| MULLIONS SHALL BE OF A DEPTH THAT PREVENTS COLD |
| SOLDERING OF ADJACENT SPRINKLERS. THE SPRINKLER DESIGN |
| SHOULD INDICATE WHICH WINDOW SPRINKLER MODEL WILL BE |
| USED (HORIZONTAL SIDEWALL OR PENDENT VERTICAL |
| SIDEWALL). |
| |
| FIRE SPRINKLER: CONFIRM THE EXISTING ATTACHED STORAGE |
| BUILDING (INDICATED AS NIC) IS PROTECTED BY THE |
| AUTOMATIC SPRINKLER SYSTEM. |
| |
| WESLEY JOLIN |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |