Date Text
2013-06-04 16:22:506-4-13
 FIRST REVIEW
 PLEASE CORRECT PANEL SCHEDULES HP2 AND LP1. THEY BOTH
 SHOW A FEED TO AHU 1-2 AND CU 1-2. PLEASE REVIEW AND
 CORRECT.
 ALSO, CU 1-3 AND 1-4 STATE A MOCP AS 15 AMPS ON THE M
 DRAWINGS. THERE IS A 20 AMP CIRCUIT BREAKER SHOWN IN
 THE PANEL SCHEDULE PLEASE CORRECT
 VB