Plan Review Notes For Permit 13050713 |
Permit Number |
13050713 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-06-04 16:22:50 | 6-4-13 | | FIRST REVIEW | | PLEASE CORRECT PANEL SCHEDULES HP2 AND LP1. THEY BOTH | | SHOW A FEED TO AHU 1-2 AND CU 1-2. PLEASE REVIEW AND | | CORRECT. | | ALSO, CU 1-3 AND 1-4 STATE A MOCP AS 15 AMPS ON THE M | | DRAWINGS. THERE IS A 20 AMP CIRCUIT BREAKER SHOWN IN | | THE PANEL SCHEDULE PLEASE CORRECT | | VB |
|