2013-06-12 12:33:34BUILDING PLAN REVIEW
 PERMIT: 13050713
 ADD: 313 DATURA ST
 CONT: ANDEERSON-MOORE CONSTRUCTION
 TEL: (561)753-7400
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JUNE 12/ 2013
 ACTION: DENIED
  
 1) ) SHEET LS-01 EXISTING STAIR # 1 THE PLANS SHOW A
 DOORWAY UNDER THE STAIR, PLEASE PROVIDE A CROSS SECTION
 AND CODE COMPLIANCE FOR 2010 FBC-B 1009.6.3 ENCLOSURES
 UNDER STAIRS.
  
 2) SHEET LS-01 THE ELEVATOR LOBBY RESTROOMS DOORS
 107-108, PLEASE REVIEW 2010 FL ACCESSIBILITY CODE
 SECTION DOORS IN SERIES 404.2.6, SEE 603.2.3 EX # 2
 THIS MAY HELP.
  
 3) SHEET A-1.01 DOOR # 11 VERSES A-6.01 INDICATES A ?
 HR DOOR. PLEASE REVIEW 2010 FBC-B
 1026.6, 1022.3 SECTION 715 TABLE 715.4 1 HR EXIT
 ENCLOSURES, 1 HR OPENING PROTECTIVE?S, ALSO REVIEW 2007
 FBC-B COMMENTARY FIGURE 1023.6(1) CROSS HATCHED AREA
 REQUIRES 1 HOUR OPENING PROTECTIVE?S WITHIN 10 FOOT OF
 DOORWAY AND LANDINGS.
  
 4) COMPLIED. 6/20/2013 SHEET A-1.01 EXIT FROM 3RD FLOOR
 TO 2ND FLOOR STAIR # 1, YOU HAVE TO LEAVE THE STAIR
 ENCLOSURE AND THEN GO BECK INTO THE STAIR ENCLOSE FROM
 THE 2ND FLOOR TO 1ST FLOOR. 2010 FEBC- 705.2, EXCEPTION
 # 2 MEANS OF EGRESS CONFORMING TO THE REQUIREMENTS OF
 THE FLORIDA BUILDING CODE, BUILDING AND THE FLORIDA
 FIRE PREVENTION CODE UNDER WHICH THE BUILDING WAS
 CONSTRUCTED SHALL BE CONSIDERED COMPLIANT MEANS OF
 EGRESS IF, IN THE OPINION OF THE CODE OFFICIAL, THEY DO
 NOT CONSTITUTE A DISTINCT HAZARD TO LIFE.BUIULDING &
 FIRE OFFICIALS AGREE CONSIDERED TO BE CODE COMPLIANT AT
 TIME BUILDING WAS BUILT.
  
 5) LS-02 VERSES A-1.01 2ND FLOOR THE PATH THAT LEADS TO
 THE NEW EXTERIOR STAIR. THE WINDOWS APPEAR TO SHOW A
 FIRE RATING AND ALSO A WATER CURTAIN. SHEET A-6.01
 INDICATES 45 MINUTE RATED, PLEASE SEE 2007 FBC-B CODE
 COMMENTARY FIGURE 1023.6(1).
  
 6) COMPLIED 6/20/2013. THIS IS A BUILDING TYPE V-B.
 ZERO LOT LINE EXTERIOR WALLS TO BE 1 HOUR FIRE SISTANCE
 RATED. THE GLASS BLOCK WILL BE CONSIDERED INFILL WALL
 AND WILL ALSO BE REQUIRED TO BE 1 HOUR RATED SINCE 2010
 FBC-B TABLE 705.8 DOES NOT ALLOW OPENINGS IN WALLS 0-3
 FEET FROM THE PROPERTY LINE.
  
 7) SHEET A-1.01 INDICATES NEW ROOF TOP A/C STANDS,
 PLEASE PROVIDE THE ATTACHMENT OF THE STANDS TO THE ROOF
 STRUCTURE AS WELL AS THE EQUIPMENT TO THE STAND.
 PLEASE REVIEW 2010 FBC-B SECTION 1609.8 ROOFTOP
 STRUCTURES AND EQUIPMENT.
  
 8) SHEET A-1.01 INDICATES NEW ROOF TOP A/C STANDS, THE
 ROOF TOP STANDS ARE WITHIN 3?-0? OF THE PARAPET,
 SECTION 5/ A-1.03 DOES NOT INDICATE HOW TALL THE
 PARAPET IS? SEE 2010 FBC-B
 1013.5 MECHANICAL EQUIPMENT.
  
 9) SHEET A-1.02 THIRD FLOOR, WINDOW # 17 AND DOOR 304
 WILL NEED TO BE 1 HOUR FIRE RATED, AGAIN 1026.6, 1022.3
 SECTION 715 TABLE 715.4 1 HR EXIT ENCLOSURES, 1 HR
 OPENING PROTECTIVE?S, ALSO REVIEW 2007 FBC-B COMMENTARY
 FIGURE 1023.6(1) CROSS HATCHED AREA REQUIRES 1 HOUR
 OPENING PROTECTIVE?S WITHIN 10 FOOT OF DOORWAY AND
 LANDINGS.
  
 10) SHEET A-5.10 KITCHEN ROOM 303 MICROWAVE HEIGHT MUST
 MEET THE REACH RANGES, PROVIDE COMPLIANCE WITH 2010 FL
 ACCESSIBILITY CODE 308 REACH RANGES AND 309 OPERABLE
 PARTS.
  
 11) A-1.01 AND S-1.01 BOTH INDICATE WHAT APPEARS TO BE
 SLOPED FLOORS, PLEASE PROVIDE THE HEIGHT DIFFERENCE IN
 FLOORS AND THE DISTANCE THE SLOPED FLOOR WILL BE, TO
 DETERMINE IF CONSIDERED GRADE OR RAMP WITH REQUIRED
 HANDRAILS. ACCESSIBILITY CODE ADVISORY 505.1 GENERAL.
 HANDRAILS ARE REQUIRED ON RAMP RUNS WITH A RISE GREATER
 THAN 6 INCHES (150 MM) (SEE 405.8) AND ON CERTAIN
 STAIRWAYS (SEE 504). HANDRAILS ARE NOT REQUIRED ON
 WALKING SURFACES WITH RUNNING SLOPES LESS THAN 1:20.
 HOWEVER, HANDRAILS ARE REQUIRED TO COMPLY WITH 505 WHEN
 THEY ARE PROVIDED ON WALKING SURFACES WITH RUNNING
 SLOPES LESS THAN 1:20 (SEE 403.6). SECTIONS 505.2,
 505.3, AND 505.10 DO NOT APPLY TO HANDRAILS PROVIDED ON
 WALKING SURFACES WITH RUNNING SLOPES LESS THAN 1:20 AS
 THESE SECTIONS ONLY REFERENCE REQUIREMENTS FOR RAMPS.
  
 12) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 13) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  