2013-06-12 12:33:34 | BUILDING PLAN REVIEW |
| PERMIT: 13050713 |
| ADD: 313 DATURA ST |
| CONT: ANDEERSON-MOORE CONSTRUCTION |
| TEL: (561)753-7400 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: JUNE 12/ 2013 |
| ACTION: DENIED |
| |
| 1) ) SHEET LS-01 EXISTING STAIR # 1 THE PLANS SHOW A |
| DOORWAY UNDER THE STAIR, PLEASE PROVIDE A CROSS SECTION |
| AND CODE COMPLIANCE FOR 2010 FBC-B 1009.6.3 ENCLOSURES |
| UNDER STAIRS. |
| |
| 2) SHEET LS-01 THE ELEVATOR LOBBY RESTROOMS DOORS |
| 107-108, PLEASE REVIEW 2010 FL ACCESSIBILITY CODE |
| SECTION DOORS IN SERIES 404.2.6, SEE 603.2.3 EX # 2 |
| THIS MAY HELP. |
| |
| 3) SHEET A-1.01 DOOR # 11 VERSES A-6.01 INDICATES A ? |
| HR DOOR. PLEASE REVIEW 2010 FBC-B |
| 1026.6, 1022.3 SECTION 715 TABLE 715.4 1 HR EXIT |
| ENCLOSURES, 1 HR OPENING PROTECTIVE?S, ALSO REVIEW 2007 |
| FBC-B COMMENTARY FIGURE 1023.6(1) CROSS HATCHED AREA |
| REQUIRES 1 HOUR OPENING PROTECTIVE?S WITHIN 10 FOOT OF |
| DOORWAY AND LANDINGS. |
| |
| 4) COMPLIED. 6/20/2013 SHEET A-1.01 EXIT FROM 3RD FLOOR |
| TO 2ND FLOOR STAIR # 1, YOU HAVE TO LEAVE THE STAIR |
| ENCLOSURE AND THEN GO BECK INTO THE STAIR ENCLOSE FROM |
| THE 2ND FLOOR TO 1ST FLOOR. 2010 FEBC- 705.2, EXCEPTION |
| # 2 MEANS OF EGRESS CONFORMING TO THE REQUIREMENTS OF |
| THE FLORIDA BUILDING CODE, BUILDING AND THE FLORIDA |
| FIRE PREVENTION CODE UNDER WHICH THE BUILDING WAS |
| CONSTRUCTED SHALL BE CONSIDERED COMPLIANT MEANS OF |
| EGRESS IF, IN THE OPINION OF THE CODE OFFICIAL, THEY DO |
| NOT CONSTITUTE A DISTINCT HAZARD TO LIFE.BUIULDING & |
| FIRE OFFICIALS AGREE CONSIDERED TO BE CODE COMPLIANT AT |
| TIME BUILDING WAS BUILT. |
| |
| 5) LS-02 VERSES A-1.01 2ND FLOOR THE PATH THAT LEADS TO |
| THE NEW EXTERIOR STAIR. THE WINDOWS APPEAR TO SHOW A |
| FIRE RATING AND ALSO A WATER CURTAIN. SHEET A-6.01 |
| INDICATES 45 MINUTE RATED, PLEASE SEE 2007 FBC-B CODE |
| COMMENTARY FIGURE 1023.6(1). |
| |
| 6) COMPLIED 6/20/2013. THIS IS A BUILDING TYPE V-B. |
| ZERO LOT LINE EXTERIOR WALLS TO BE 1 HOUR FIRE SISTANCE |
| RATED. THE GLASS BLOCK WILL BE CONSIDERED INFILL WALL |
| AND WILL ALSO BE REQUIRED TO BE 1 HOUR RATED SINCE 2010 |
| FBC-B TABLE 705.8 DOES NOT ALLOW OPENINGS IN WALLS 0-3 |
| FEET FROM THE PROPERTY LINE. |
| |
| 7) SHEET A-1.01 INDICATES NEW ROOF TOP A/C STANDS, |
| PLEASE PROVIDE THE ATTACHMENT OF THE STANDS TO THE ROOF |
| STRUCTURE AS WELL AS THE EQUIPMENT TO THE STAND. |
| PLEASE REVIEW 2010 FBC-B SECTION 1609.8 ROOFTOP |
| STRUCTURES AND EQUIPMENT. |
| |
| 8) SHEET A-1.01 INDICATES NEW ROOF TOP A/C STANDS, THE |
| ROOF TOP STANDS ARE WITHIN 3?-0? OF THE PARAPET, |
| SECTION 5/ A-1.03 DOES NOT INDICATE HOW TALL THE |
| PARAPET IS? SEE 2010 FBC-B |
| 1013.5 MECHANICAL EQUIPMENT. |
| |
| 9) SHEET A-1.02 THIRD FLOOR, WINDOW # 17 AND DOOR 304 |
| WILL NEED TO BE 1 HOUR FIRE RATED, AGAIN 1026.6, 1022.3 |
| SECTION 715 TABLE 715.4 1 HR EXIT ENCLOSURES, 1 HR |
| OPENING PROTECTIVE?S, ALSO REVIEW 2007 FBC-B COMMENTARY |
| FIGURE 1023.6(1) CROSS HATCHED AREA REQUIRES 1 HOUR |
| OPENING PROTECTIVE?S WITHIN 10 FOOT OF DOORWAY AND |
| LANDINGS. |
| |
| 10) SHEET A-5.10 KITCHEN ROOM 303 MICROWAVE HEIGHT MUST |
| MEET THE REACH RANGES, PROVIDE COMPLIANCE WITH 2010 FL |
| ACCESSIBILITY CODE 308 REACH RANGES AND 309 OPERABLE |
| PARTS. |
| |
| 11) A-1.01 AND S-1.01 BOTH INDICATE WHAT APPEARS TO BE |
| SLOPED FLOORS, PLEASE PROVIDE THE HEIGHT DIFFERENCE IN |
| FLOORS AND THE DISTANCE THE SLOPED FLOOR WILL BE, TO |
| DETERMINE IF CONSIDERED GRADE OR RAMP WITH REQUIRED |
| HANDRAILS. ACCESSIBILITY CODE ADVISORY 505.1 GENERAL. |
| HANDRAILS ARE REQUIRED ON RAMP RUNS WITH A RISE GREATER |
| THAN 6 INCHES (150 MM) (SEE 405.8) AND ON CERTAIN |
| STAIRWAYS (SEE 504). HANDRAILS ARE NOT REQUIRED ON |
| WALKING SURFACES WITH RUNNING SLOPES LESS THAN 1:20. |
| HOWEVER, HANDRAILS ARE REQUIRED TO COMPLY WITH 505 WHEN |
| THEY ARE PROVIDED ON WALKING SURFACES WITH RUNNING |
| SLOPES LESS THAN 1:20 (SEE 403.6). SECTIONS 505.2, |
| 505.3, AND 505.10 DO NOT APPLY TO HANDRAILS PROVIDED ON |
| WALKING SURFACES WITH RUNNING SLOPES LESS THAN 1:20 AS |
| THESE SECTIONS ONLY REFERENCE REQUIREMENTS FOR RAMPS. |
| |
| 12) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 13) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |