2013-05-28 10:03:15515 NORTH FLAGLER DRIVE - SUITE #1800
 PERMIT #13050695
 MASTER #13030512
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FOR SYSTEM PRESSURES EXCEEDING 100 PSI, ARMOVERS AND
 END OF BRANCH LINE PENDENT SPRINKLERS SHALL BE
 PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL BE
 LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  