Plan Review Notes For Permit 13050642 |
Permit Number |
13050642 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-06-07 15:32:37 | RESIDENTIAL (R3) RENOVATION PLUMBING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- FLOOR PLAN SUBMITTED IS INCOMPLETE. PROVIDE COMPLETE | | FLOOR PLAN SHOWING BATHROOMS, KITCHEN AND LAUNDRY ROOM | | LAYOUTS. CLARIFY WHAT IS NEW AND WHAT'S EXISTING. WHAT | | IS GOING TO BE EXACT FIXTURE REPLACEMENT TO CLARIFY | | SCOPE OF WORK. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | 2- PROVIDE PLUMBING RISER DIAGRAM. SEC. 107.3.5.3(11) | | OF CITY AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|