Plan Review Notes
Plan Review Notes For Permit 13050642
Permit Number 13050642
Review Stop E
Sequence Number 1
Notes
Date Text
2013-05-23 09:36:115-23-13
  
 1. ELECTRICAL PERMIT REQUIRED
 2. PROVIDE CUT SHEETS FOR AIR CONDIRTIONING EQUIPMENT
 TO BE INSTALLED
 3. CORRECT AC CIRCUITS IN PANEL SCHEDULE TO "2-POLE"
 4. ALL NEW CIRCUITS TO BE AFCI PROTECTED PER NEC210.12B
 5. TAMPER RESISTANT RECEPTACLES REQUIED IF ANY NEW
 INSTALLED PER NEC 406.11
 VB