Notes |
Date |
Text |
2013-05-23 09:36:11 | 5-23-13 | | | | 1. ELECTRICAL PERMIT REQUIRED | | 2. PROVIDE CUT SHEETS FOR AIR CONDIRTIONING EQUIPMENT | | TO BE INSTALLED | | 3. CORRECT AC CIRCUITS IN PANEL SCHEDULE TO "2-POLE" | | 4. ALL NEW CIRCUITS TO BE AFCI PROTECTED PER NEC210.12B | | 5. TAMPER RESISTANT RECEPTACLES REQUIED IF ANY NEW | | INSTALLED PER NEC 406.11 | | VB |
|