2013-06-01 10:24:44 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| 1. PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| THAT THIS PARCEL IS LOCATED IN THE 165 MPH WIND ZONE. |
| SEE HTTP://WWW.ATCOUNCIL.ORG/WINDSPEED; |
| LATITUDE/LONGITITUDE INFORMATION SHOWS THIS PARCEL AS |
| 168MPH MINIMUM, FBC R 301. |
| |
| 2. SEE COMMENT #1, ROOF PRESSURES APPEAR LOW. CHECK ALL |
| DESIGN PRESSURES. CALCULATIONS MAY BE REQUIRED. BASED |
| ON FBC TABLE R 301.2(2), ZONE 3 FOR FLAT DECK SHOULD BE |
| -95.7, BUT -84.1 SPECIFIED ON PLAN. |
| |
| 3. REVISE THE FLOOR PLAN TO SHOW CLEAR OPENING (HEIGHT, |
| WIDTH, TOTAL SF) FOR BEDROOM EGRESS WINDOWS. IF NON |
| COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE |
| PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF |
| WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED |
| CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB |
| 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN |
| 5%. |
| |
| 4. SEE PAGE 9 OF THE FLAT DECK NOA AND "ENHANCED |
| NAILING CALCULATIONS" . FASTENING FOR ZONE 1 PROPOSED |
| BY ENGINEER NOT CONSISTENT WITH THE NOA (12" RATHER |
| THAN 8"). NUMBER OF FIELD ROWS NOT SPECIFIED. IF USING |
| GENERAL LIMITATION #6 IS PROPOSED, PROVIDE |
| CALCULATIONS. |
| |
| 5. FASTENING PATTERN "ENHANCED NAILING CALCULATIONS" DO |
| NOT INCLUDE NUMBE OF ROWS. PLEASE REVISE AND BE CLEAR |
| AS TO WHETHER THE NUMBER OF ROWS REQUIRED INCLUDES THE |
| LAP ROW. |
| |
| 6. ENERGY CALCS (FORM 402-2010) DO NOT INCLUDE A/C |
| SYSTEM INFO, PLEASE REVISE. |
| |
| 7. THE TWO FLORIDA STATE PRODUCT APPROVALS SUBMITTED |
| (DOOR AND ANCHORS) INCLUDED ONLY THE COVER SHEET. THE |
| EVALUATION REPORT AND INSTALLATION INSTRUCTIONS ARE |
| REQUIRED, FBC R 301. |
| |
| |