Plan Review Notes For Permit 13050618 |
Permit Number |
13050618 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-06-14 15:54:32 | 2010 FBC / 2008 NEC | | | | DENIED BY ELECTRICAL | | | | 1) SUBMIT TWO SETS OF ELECTRICAL PLANS SHOWING THE | | LOCATIONS OF EXISTING AND RELOCATED OUTLETS AND THAT | | ALL WORK COMPLIES WITH THE 2008 NATIONAL ELECTRICAL | | CODE. CITY AMENDMENTS 107.2.1 | | | | 2) MULTIWIRE BRANCH CIRCUITS ARE REQUIRED TO COMPLY | | WITH NEC 210.4. | | | | 3) ARC-FAULT PROTECTION IS REQUIRED TO COMPLY WITH NEC | | 210.4. | | | | 4) TAMPER RESISTANT RECEPTACLES ARE REQUIRED TO COMPLY | | WITH NEC 406.11. | | | | 5) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR REQUIRED SMOKE | | DETECTORS. | | | | 6) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE PERSON | | RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS. | | CITY AMENDMENTS 107.2.1 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|