Plan Review Notes
Plan Review Notes For Permit 13050618
Permit Number 13050618
Review Stop E
Sequence Number 1
Notes
Date Text
2013-06-14 15:54:322010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) SUBMIT TWO SETS OF ELECTRICAL PLANS SHOWING THE
 LOCATIONS OF EXISTING AND RELOCATED OUTLETS AND THAT
 ALL WORK COMPLIES WITH THE 2008 NATIONAL ELECTRICAL
 CODE. CITY AMENDMENTS 107.2.1
  
 2) MULTIWIRE BRANCH CIRCUITS ARE REQUIRED TO COMPLY
 WITH NEC 210.4.
  
 3) ARC-FAULT PROTECTION IS REQUIRED TO COMPLY WITH NEC
 210.4.
  
 4) TAMPER RESISTANT RECEPTACLES ARE REQUIRED TO COMPLY
 WITH NEC 406.11.
  
 5) SHOW COMPLIANCE WITH FBCR 314.3.1 FOR REQUIRED SMOKE
 DETECTORS.
  
 6) THE NAME, SIGNATURE AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS.
 CITY AMENDMENTS 107.2.1
  