Plan Review Notes
Plan Review Notes For Permit 13050597
Permit Number 13050597
Review Stop B
Sequence Number 1
Notes
Date Text
2013-05-24 13:46:31PROVISO:
 PROVIDE DOCUMENTATION THAT ELECTRIC LOCK MEETS THE
 FOLLOWING CODE COMPLIANCE:
 2010 FBC-B 1008.1.4.4. ACCESS-CONTROLLED EGRESS DOORS.
 THE ENTRANCE DOORS IN A MEANS OF EGRESS IN BUILDINGS
 WITH AN OCCUPANCY IN GROUP A, B, D, E, I-2, M, R-1 OR
 R-2 AND ENTRANCE DOORS TO TENANT SPACES IN OCCUPANCIES
 IN GROUPS A, B, D, E, I-2, M, R-1 AND R-2 ARE PERMITTED
 TO BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS
 ACCESS CONTROL SYSTEM WHICH SHALL BE INSTALLED IN
 ACCORDANCE WITH ALL OF THE FOLLOWING CRITERIA:
  
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE
 ARRANGED TO DETECT AN OCCUPANT APPROACHING THE DOORS.
 THE DOORS SHALL BE ARRANGED TO UNLOCK BY A SIGNAL FROM
 OR LOSS OF POWER TO THE SENSOR.
  
 2. LOSS OF POWER TO THAT PART OF THE ACCESS CONTROL
 SYSTEM WHICH LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS.
  
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK FROM A MANUAL
 UNLOCKING DEVICE LOCATED 40 INCHES TO 48 INCHES (1016
 MM TO 1219 MM) VERTICALLY ABOVE THE FLOOR AND WITHIN 5
 FEET (1524 MM) OF THE SECURED DOORS. READY ACCESS SHALL
 BE PROVIDED TO THE MANUAL UNLOCKING DEVICE AND THE
 DEVICE SHALL BE CLEARLY IDENTIFIED BY A SIGN THAT READS
 ?PUSH TO EXIT.? WHEN OPERATED, THE MANUAL UNLOCKING
 DEVICE SHALL RESULT IN DIRECT INTERRUPTION OF POWER TO
 THE LOCK?INDEPENDENT OF THE ACCESS CONTROL SYSTEM
 ELECTRONICS?AND THE DOORS SHALL REMAIN UNLOCKED FOR A
 MINIMUM OF 30 SECONDS.
  
 4. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM, IF
 PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOORS, AND THE
 DOORS SHALL REMAIN UNLOCKED UNTIL THE FIRE ALARM SYSTEM
 HAS BEEN RESET.
  
 5. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOORS. THE DOORS SHALL REMAIN UNLOCKED UNTIL
 THE FIRE ALARM SYSTEM HAS BEEN RESET.
  
 6. ENTRANCE DOORS IN BUILDINGS WITH AN OCCUPANCY IN
 GROUP A, B, E OR M SHALL NOT BE SECURED FROM THE EGRESS
 SIDE DURING PERIODS THAT THE BUILDING IS OPEN TO THE
 GENERAL PUBLIC