Plan Review Notes For Permit 13050592 |
Permit Number |
13050592 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-05-17 17:04:42 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA | | 08-0410.09 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. | | | | 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | 08-0410.09 SUBMITTED. NEED THE RAS 117 CALCULATIONS TO | | MEET THE DESIGN PRESSURES OF SEC. R301.2.1.4.3 OF 2010 | | FBC-RESIDENTIAL. | | | | 3- PROVIDE 2 COPIES OF THE PRODUCT APPROVAL. ONLY ONE | | WAS SUBMITTED. SEC. 107.1 CITY AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|