Plan Review Notes
Plan Review Notes For Permit 13050592
Permit Number 13050592
Review Stop B
Sequence Number 1
Notes
Date Text
2013-05-17 17:04:42RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA
 08-0410.09 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 08-0410.09 SUBMITTED. NEED THE RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES OF SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL.
  
 3- PROVIDE 2 COPIES OF THE PRODUCT APPROVAL. ONLY ONE
 WAS SUBMITTED. SEC. 107.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL