 1. PROVIDE LOAD CALCULATIONS PER NEC 220
 2. FLUORESCENT FIXTURES TO MEET NEC 410.130G
 3. LIGHTING CONTROLS REQUIRED PER FLORIDA ENERGY CODE
 505.2.2
 4. IDENTIFY DISCONNECTS PER NEC 110.22A
 5. PER NEC 210.62, SHOW WINDOW RECEPTACLES ARE REQUIRED
 FOR EVERY 12 FT OF STORE FRONT