Plan Review Notes For Permit 13050533 |
Permit Number |
13050533 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-05-23 10:16:31 | 5-23-13 | | | | 1. PROVIDE LOAD CALCULATIONS PER NEC 220 | | 2. FLUORESCENT FIXTURES TO MEET NEC 410.130G | | 3. LIGHTING CONTROLS REQUIRED PER FLORIDA ENERGY CODE | | 505.2.2 | | 4. IDENTIFY DISCONNECTS PER NEC 110.22A | | 5. PER NEC 210.62, SHOW WINDOW RECEPTACLES ARE REQUIRED | | FOR EVERY 12 FT OF STORE FRONT | | VB |
|