2013-05-30 16:52:25 | BUILDING PLAN REVIEW |
| REVISION: 13050499 |
| PERMIT: 13040277 |
| ADD: 1801 S FLAGLER # 1711 |
| CONT: FRED BLANK & ASSOCIATES |
| TEL: (561)309-7638 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MAY 30/2013 |
| ACTION: BUILDING PROVISO |
| |
| 1) PLEASE PROVIDE A CROSS SECTION OF THE BUILT UP |
| SHOWER WITH THE FINISH FLOOR 10 INCHES AFF. PROVIDE |
| FRAMING MATERIALS, TYPES OF DECK AND WALL SUB-STRATE |
| MATERIALS, PROVIDE THE |
| CLEAR HEIGHT FROM THE FINISHED SHOWER FLOOR TO BATHROOM |
| CEILING. PROVIDE DETAIL OF STEP INTO THE SHOWER. |
| |
| 2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE |
| MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR |
| II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN |
| ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3: |
| 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS |
| REQUIRED. |
| |
| 2509.2 BASE FOR TILE. |
| GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT |
| SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288 |
| OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| |
| JAMES A. WITMER CBO |