 PERMIT #13050496
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE SYSTEM WILL NEED TO BE PRESSURE TESTED TO 200 PSI
 BECAUSE BRANCH LINE PIPING HAS BEEN ADDED; IE THIS IS
 NOT A SIMPLE HEAD RELOCATION.
  
 REVISED HYDRAULIC CALCULATIONS WILL NEED TO BE
 SUBMITTED SHOWING THE USE AND ADDITIONAL FRICTION LOSS
 ASSOCIATED WITH THE VICFLEX FLEXIBLE SPRINKLER DROPS.
  