Plan Review Notes
Plan Review Notes For Permit 13050493
Permit Number 13050493
Review Stop B
Sequence Number 1
Notes
Date Text
2013-05-15 18:09:04****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THIS APPEARS TO BE LOCATED IN EXPOSURE C, SEE FBC R
 301.2.1.4.3. PROVIDE MEAN ROOF HEIGHT. FOR 15' MRH,
 ZONE 3 DP REQUIRED PER FBC R TABLE 301.2(2) IS -95.7;
 FOR 20' IT IS -102. DESIGN PRESSURE OF -90 PROPOSED
 DOES NOT COMPLY WITH THE TABLE.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FAC9N-3. PROVIDE COVER SHEET FOR THE EVALUATION REPORT.
  
  
  