Plan Review Notes For Permit 13050441 |
Permit Number |
13050441 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-08-29 08:11:57 | PROVISO REVISION REQUIRED SEE DIGITAL SHEET A7.01: | | | | 1) SEE HIGHLIGHTED AREA ACCESS AISLE MINIMUM WIDTH | | REQUIRED 44 INCHES OCCUPANT LOAD SEERVING > 50 | | OCCUPANTS. FBC-B 1028.9.1. CURRENT WIDTH OF 2.34 FEET. | | | | 2) SECOND AREA OF COMPLIANCE REQUIRED, COMPLY WITH | | FBC-B 1017.3 AISLE ACCESSWAY SHALL NOT EXCEED 30 FEET | | FROM ANY SEAT TO THE POINT WHERE A PERSON HAS TWO | | CHOICES OR MORE PATHS OF EGRESS TRAVEL TO SEPERATE | | EXITS. |
|