2013-05-15 17:36:37 | ROOFING REVISION BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | 08-0410.09 SUBMITTED. NEED THE CALCULATIONS TO MEET THE | | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3 OF 2010 | | FBC. | | | | ***NOTE: | | DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS TO | | TAKE INTO CONSIDERATION THAT THIS PROPERTY IS LOCATED | | ON EXPOSURE "D". | | | | | | 2- THERE IS AN ENGINEER ON BOARD FOR THIS PROJECT. | | ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE PRODUCT | | APPROVAL IN WRITING AS REQUIRED BY SEC. 107.3.4 OF CITY | | AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|