Plan Review Notes
Plan Review Notes For Permit 13050330
Permit Number 13050330
Review Stop M
Sequence Number 1
Notes
Date Text
2013-05-10 10:52:26PLAN DENIED
 1) PROVIDE CFM ON THE PLAN AT EACH GRILLE.
 PER SECTION 107 FCB 2010
 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 EXCEPTION # 2 TRANSFER GRILLES.
 3) REFER TO FLORIDA STATUTES 471.003 ENGINEERING
 QUALFICATIONS FOR PRACTICE SECTION 2 H
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved