Plan Review Notes For Permit 13050215 |
Permit Number |
13050215 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-05-31 15:26:56 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) SUBMIT PRODUCT APPROVALS FOR THE ROOFING MATERIAL | | AND THE SIMPSON CONNECTORS AND ANCHORS SPECIFIED ON THE | | PLANS. DCA RULE 9N-3 | | | | 2) SPECIFY THE ROOF SHEATHING MATERIAL AND THE | | FASTENERS AND SPACING. FBC R803 | | | | 3) THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR | | THE DESIGN IS REQUIRED ON THE PLANS. CITY AMENDMENTS | | 107.2.1 | | | | 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | THE PROJECT. CITY AMENDMENTS 107.3.4.1 | | | | 5) THE ROOF UPLIFT CALCULATIONS AND BASE SHEET FASTENER | | SPACING INFORMATION ON THE PLANS ARE ILLEGIBLE. PLEASE | | CORRECT. | | | | 6) THE PLANS SPECIFY GWB (GYPSUM WALL BOARD) ON THE | | CEILING OF THE OPEN PORCH. GWB IS NOT AN ACCEPTED | | EXTERIOR COVERING. SEE FBC R703.1 SUBMIT TWO COPIES OF | | THE PRODUCT APPROVALS FOR THE GWB THAT IS SPECIFIED AS | | THE CLADDING FOR THE EXTERIOR PORCH CEILING AS REQUIRED | | BY DCA RULE 9N-3. | | | | 7) SHOW COMPLIANCE WITH FBC R314.3.1 FOR REQUIRED SMOKE | | ALARMS. | | | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|