Plan Review Notes For Permit 13050212 |
Permit Number |
13050212 |
|
Review Stop |
Z |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-07-29 15:25:24 | FAILED | | | | 1) NEW STRUCTURAL DETAILS WERE NOT SUBMITTED TO SHOW | | THE ROOF STRUCTURAL SUPPORT MEETING THE REQUIRED REAR | | SETBACK OF 10 FEET. THE ORIGINALLY SUBMITTED | | ENGINEERING SHOWS THE SUPPORTS VIOLATING THE SET BACK | | AND MAY NOT BE USED FOR THE CHANGED CONFIGURATION. | | | | 2) THE LEFT AND RIGHT ELEVATIONS SHOW LUMITE SCREEN AND | | REGULAR SCREEN EXTENDING PAST THE 10 FOOT REAR SETBACK | | LINE. WHILE THE ROOF IS PERMITTED TO OVERHANG INTO THE | | SETBACK, THERE IS NO CONSTRUCTION ALLOWED UNDER IT. | | THIS WOULD NO LONGER BE AN OVERHANG, BUT RATHER AN | | EXTENSION OF THE PRIMARY STRUCTURE. | | | | 3) THE ROOF OVERHANG IS 42 INCHES (2' 6" PLUS 12") NOT | | 36 INCHES AS PERMITTED BY THE OAKTON COMMONS DESIGN | | GUIDELINES. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|