2013-05-17 13:31:59RESIDENTIAL (R3) RENOVATIONS, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOW MULLIONS, INCLUDING WINDOW MULLIONS FOR BAY
 WINDOW IN DINING AREA.
  
 B) ROOF RIDGE VENT.
  
 C) FLAT ROOF. NOA 12-0227.18 SUBMITTED WAS SUPERSEDED
 BY MIAMI-DADE. VISIT THE MIAMI DADE WEBSITE AND
 DOWNLOAD CURRENT NOA.
 AND, PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 TO MEET THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL.
  
 ***NOTE: IF NOA SUBMITTED REQUIRES RAS 117 CALCULATIONS
 TO BE SIGNED AND SEALED, THEN PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS.
  