2013-05-17 14:37:09 | 5-17-13 | | | | PROVIDE PANEL SCHEDULE - NEC 408.4A | | PROVIDE LOAD CALCS INCLUDING ALL NEW AND EXISTING LOADS | | - NEC 220 | | ADD FEEDER RISER DIAGRAM - NEC 215.5 | | ALL RECEPTACLES TO BE TAMPER RESISTANT - NEC 406.11 | | ALL REQUIRED RECEPTS TO BE AFCI PROTECTED - NEC 210.12B | | BALCONY RECEPTS TO BE GFCI - NEC 210.8.A.3 | | ALL WORK TO COMPLY WITH 2008 NEC | | SHOW CIRCUIT NUMBERS ON FLOOR PLAN | | MULTIWIRE CIRCUITS SHALL MEET NEC 210.4 | | USE DEEP BOXES FOR 3 OR MORE CABLE ENTRIES TO ENSURE | | REQUIRED BOX FILL MINIMUM NEC 314.16 | | VB | | | | |
|