 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SUBMIT PRODUCT DATA FOR FUTURE VENTLESS FRYER COMPLYING
 WITH FBCM 507.1(#2); OTHERWISE THE FOLLOWING WILL BE
 REQUIRED:
  
 DEEP FAT FRYER: COOKING OPERATIONS PRODUCING SMOKE OR
 GREASE-LADEN VAPORS SHALL BE PROTECTED WITH A CLASS I
 MECHANICAL EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC
 WET-CHEMICAL FIRE SUPPRESSION SYSTEM.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL BE
 LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10
 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST
 SYSTEM. THE DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE
 THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
  
 PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND
 ASSOCIATED SIGNAGE IN KITCHEN AREA.
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
  