| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| SUBMIT PRODUCT DATA FOR FUTURE VENTLESS FRYER COMPLYING |
| WITH FBCM 507.1(#2); OTHERWISE THE FOLLOWING WILL BE |
| REQUIRED: |
| |
| DEEP FAT FRYER: COOKING OPERATIONS PRODUCING SMOKE OR |
| GREASE-LADEN VAPORS SHALL BE PROTECTED WITH A CLASS I |
| MECHANICAL EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC |
| WET-CHEMICAL FIRE SUPPRESSION SYSTEM. |
| |
| DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE |
| SURFACE. |
| |
| PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL BE |
| LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10 |
| FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST |
| SYSTEM. THE DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE |
| THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD |
| PROTECTED. |
| |
| PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND |
| ASSOCIATED SIGNAGE IN KITCHEN AREA. |
| |
| KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE |
| BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE |
| ALARM CONDITION. |
| |