Plan Review Notes
Plan Review Notes For Permit 13050152
Permit Number 13050152
Review Stop E
Sequence Number 1
Notes
Date Text
2013-05-06 16:03:185-06-13
 1. PROVIDE ENGINEERED DRAWING FOR CEILING MOUNTER 30KVA
 TRANSFORMER
 2. PROVIDE PANEL SCHEDULE FOR MSB. SHOW AIC AND FAUILT
 CURRENT NEC 110.9 & 110.10
 3. IS PANEL SCHEDULED SHOWN ON E4 "K" OR "K2"? PLEASE
 SHOW BOTH SCHEDULES. NEC 408.4
 VB