Plan Review Notes For Permit 13050152 |
Permit Number |
13050152 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-05-06 16:03:18 | 5-06-13 | | 1. PROVIDE ENGINEERED DRAWING FOR CEILING MOUNTER 30KVA | | TRANSFORMER | | 2. PROVIDE PANEL SCHEDULE FOR MSB. SHOW AIC AND FAUILT | | CURRENT NEC 110.9 & 110.10 | | 3. IS PANEL SCHEDULED SHOWN ON E4 "K" OR "K2"? PLEASE | | SHOW BOTH SCHEDULES. NEC 408.4 | | VB |
|