Date |
Text |
2013-05-30 11:48:17 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) PROVIDE PARAPET WALL FRAMING DETAILS. SPECIFY STUD |
| SPACING, ANCHORS AND STRAPPING NEEDED TO PROVIDE A |
| CONTINUOUS LOAD PATH. FBC R301.1 AND R601.2 |
| |
| 2) SPECIFY THE ROOF AND WALL SHEATHING FASTENING |
| REQUIREMENTS ON THE PLANS. FBC R803.2.3.1 AND R604.3 |
| |
| 3) SHOW COMPLIANCE WITH FBC R703.2 FOR THE REQUIRED |
| WATER RESISTIVE BARRIER AND R703.6.3 FOR THE REQUIRED |
| BOND BREAK BETWEEN THE WATER RESISTIVE BARRIER AND THE |
| STUCCO. |
| |
| 4) SHOW COMPLIANCE WITH FBC R806.1 FOR ROOF |
| VENTILATION. |
| |
| 5) THE MINIMUM ROOF SLOPE REQUIRED FOR MODIFIED BITUMEN |
| ROOFING IS 1/4" PER FOOT PER FBC R905.11. PLEASE |
| CORRECT PLANS. |
| |
| 6) THE DOWNSPOUTS FOR THE ROOF SCUPPERS ARE REQUIRED TO |
| DISCHARGE A MINIMUM OF 1 FOOT FROM THE EXTERIOR WALLS. |
| FBC R318.6 |
| |
| 7) THE ROOF PLAN ON A-01 HAS ID MARKS 'A' AND 'D' WHICH |
| APPEAR TO BE FOR THE TRUSS ANCHORS. THE ANCHOR SCHEDULE |
| HAS MARKS 'A' AND 'B' FOR THE TRUSS ANCHORS. PLEASE |
| CLARIFY. THE TRUSS ANCHORS THAT ARE SPECIFIED IN THE |
| ANCHOR SCHEDULE DO NOT APPEAR TO BE THE CORRECT ONES |
| FOR THE APPLICATION. PLEASE REVIEW. CITY AMENDMENTS |
| 107.2.1 |
| |
| 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS AS REQUIRED |
| BY DCA RULE 9N-3 FOR THE ROOF COVERING MATERIAL |
| (INCLUDE RAS 117 CALCULATIONS FOR ENHANCED FASTENING), |
| THE TRUSS ANCHORS AND OTHER STRAPS OR CONNECTORS. |
| |
| 9) THE CC-816 COLUMN IS SPECIFIED AS 16" X 16" ON A-02 |
| AND IN THE SCHEDULE ON SHEET A-00 AN 8" X 16" COLUMN IS |
| SHOWN FOR CC-816. PLEASE CLARIFY. CITY AMENDMENTS |
| 107.2.1 |
| |