Plan Review Notes For Permit 13050042 |
Permit Number |
13050042 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-05-10 13:09:51 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | FROM PREVIOUS LIST: | | | | 1. THIS APPEARS TO BE LOCATED IN EXPOSURE C, SEE FBC R | | 301.2.1.4.3. REVISE WIND LOAD CHART AND INSTALLATION | | SCHEDULE ACCORDINGLY. | | | | 2ND REVIEW - REVISED WIND LOAD CHART PROVIDED, BUT | | INSTALLATION SCHEDULE WAS NOT REVISED. DESIGN PRESSURES | | ON INSTALLATION SCHEDULE TO COMPLY WITH EXPOSURE C | | REQUIREMENTS. | | |
|